Skip to main content

Hydrogen Leak from Flow Meter

Severity
Incident
Was Hydrogen Released?
Yes
Was There Ignition?
No
Incident Date
Incident Attributes
Setting
Damage and Injuries
Probable Cause
Contributing Factors
When Incident Was Discovered
Describe the incident, including corrective steps taken and their result.

A hydrogen gas detector on the ground floor of a building registered the release of a small amount of hydrogen gas and actuated automatic alarms both at the fire department and in one of its buildings. Additionally, interlocks connected to the gas detector completely shut down the experiment. Upon hearing the alarm, all occupants (about 6) promptly left the building. Fire department personnel are housed in the trailer next to a building and responded within one minute. They tested the atmosphere within the building, reset the gas detector, and secured the alarm at 9:15. The alarm was actuated when an experimenter assigned to the experiment was evacuating lines using a vacuum pump.

The speed of evacuation was controlled by a commercially manufactured flow meter. It is believed that the 0-ring in the manually operated valve had deteriorated and that a small amount of hydrogen gas escaped while the valve was being turned. The flow was set at approximately 1 l/min at a pressure of only 6 psi. The gas detector is located within 30cm of the valve so the time from release to solenoid activation should be less than one second. Using these criteria, it is estimated that the total release of hydrogen gas is less than l cc.

Sufficient testing and investigation has confirmed that a minimal amount of hydrogen escaped around a failed O-ring located in the valve of the commercially manufactured flow meter (direct and root cause). A significant contributing cause is the lack of a stop to prevent the valve from being opened to the point of the O-ring being damaged or distorted by contact with the threads of the valve. The flow meter in question is used only in the gas evacuation process so is opened to it's fullest extent at least daily. Although we have confirmed that no caution against over turning exists in the manuals accompanying the flow meters, we believe that this may have led to premature failure of the O-ring.

Lessons Learned

All safety devices worked as designed thereby protecting the environment and laboratory personnel. Researchers involved in the experiment acted properly and with the parameters set forth in operational procedures.

Follow up: Stops have been added to the apparatus to prevent the valves from being opened too far and exposing the 0-ring seals to damage.

Key:

  • = No Ignition
  • = Explosion
  • = Fire
Hydrogen Incident Summaries by Equipment and Primary Cause/Issue
Equipment / CauseEquipment Design or SelectionComponent FailureOperational ErrorInstallation or MaintenanceInadequate Gas or Flame DetectionEmergency Shutdown ResponseOther or Unknown
Hydrogen Gas Metal Cylinder or Regulator 3/31/2012
4/30/1995
2/6/2013
4/26/201012/31/1969  3/17/1999
11/1/2001
12/23/2003
Piping/Valves4/4/2002
2/2/2008
5/11/1999
4/20/1987
11/4/1997
12/31/1969
8/19/1986
7/27/1991
12/19/2004
2/6/2008
10/3/2008
4/5/2006
5/1/2007
9/19/2007
10/31/1980
2/7/20091/24/1999
2/24/2006
6/8/1998
12/31/1969
2/7/2009
9/1/1992
10/31/1980
10/3/2008 
Tubing/Fittings/Hose 9/23/1999
8/2/2004
8/6/2008
9/19/2007
1/1/19829/30/2004
10/7/2005
 10/7/2005 
Compressor 10/5/2009
6/10/2007
8/21/2008
1/15/2019
  10/5/20098/21/2008 
Liquid Hydrogen Tank or Delivery Truck4/27/198912/19/2004
1/19/2009
8/6/200412/31/1969 1/1/197412/17/2004
Pressure Relief Device7/25/2013
5/4/2012
1/15/2002
1/08/2007
12/31/1969    
Instrument1/15/20193/17/1999
12/31/1969
2/6/2013
  11/13/73  
Hydrogen Generation Equipment7/27/1999  10/23/2001   
Vehicle or Lift Truck 7/21/2011    2/8/2011
12/9/2010
Fuel Dispenser 8/2/2004
5/1/2007
6/11/2007
9/19/2007
 2/24/2006
1/22/2009
   
Fuel Cell Stack      5/3/2004
12/9/2010
2/8/2011
Hydrogen Cooled Generator   12/31/1969
2/7/2009
   
Other (floor drain, lab
anaerobic chamber,
heated glassware,
test chamber,
gaseous hydrogen
composite cylinder,
delivery truck)
 11/14/1994
7/21/2011
7/27/1999
6/28/2010
8/21/2008
12/31/1969
3/22/2018
  6/10/2019
  • = No Ignition
  • = Explosion
  • = Fire
We are professional and reliable provider since we offer customers the most powerful and beautiful themes. Besides, we always catch the latest technology and adapt to follow world’s new trends to deliver the best themes to the market.

Contact info

We are the leaders in the building industries and factories. We're word wide. We never give up on the challenges.

Recent Posts