Skip to main content

System Maintenance - Service - Cleanliness

What is the importance of H2 system cleanliness to safety, and what are recommended cleanliness levels for components and best practices when opening up H2 systems for maintenance/service?

The cleanliness of an H2 piping system is often based on end use requirements since the purity of the system may impact the end use application. Cleanliness required for end use purity is usually much greater than that required to prevent condensation or oxygen content sufficient to create a safety risk. While not required for the same safety reasons as oxygen safety, specifying a system to be “oxygen clean” for systems where a moderate level of cleanliness is required is a typical practice.

 Documents such as CGA 4.1 provide instruction and inspection guidelines for oxygen cleaning. Systems that require very high purity, such as for electronics, will have custom cleaning specifications for that application. One safety-related cleanliness consideration is filtering of particulates since they can cause regulators and safety valves to not operate correctly. This is a frequent concern on recently assembled lines that can have residue from machining, thread cutting, and welding.


Proper purging procedures should be used when opening a system for maintenance to ensure that a flammable mixture of hydrogen can’t be formed when the system is exposed to air. Connections should be covered when open to avoid entry of particles and moisture. Moisture is a particular concern when opening LH2 lines since water vapor can condense on cold surfaces and result in plugging of lines over time.
 

FAQ Category
FAQ Keyword
Submission Year
2023
Month
03

Ignitable Mixtures

Are the pockets of 20-35% of hydrogen in air potentially ignitable mixtures? The project in question is concerned with predicting the outcome of hydrogen air mixing in a small area (6 inches) of pipe. Process gas flows at a max of 21 scfm and consists of hydrogen primarily and some hydrocarbons that need to be treated in an incinerator. The process flows some 30 feet in a 3-inch pipe. To enable combustion, air is needed to premix with the hydrogen to enable the hydrocarbons to oxidize. Since the air and hydrogen need to be pulled into the burner, downstream of the burner is a large air blower that creates a suction (-6 inches of water) in the air and process line. The air is brought in an 8-inch pipe. The hydrogen transitions from 3 to 4 to 8 inches and mixes with air. That transition area is where the model shows mixing occurs and there are pockets of 20-35% of hydrogen in air. All the pipes are open, with one leading to the burner and the other leading to the process source. The pipes are capable of handling 1200 psi when newly installed.

Yes, these would be ignitable mixtures.  In this case, it does not appear complicated geometry is involved, so 1200 psig pipe should be more than adequate to protect against internal deflagration. The most likely scenario is a "backfire," similar to a car, where ignition occurs too soon and shoots out the open end of the pipe. Consider using an inline deflagration flash arrestor on the supply line to protect upstream piping and equipment. Also, make sure pipe welds, fittings, and instruments have a comparable rating. The pipe needs to withstand an over-pressure resulting from an ignition at the mixing point of H2-O2. This is the issue that necessitates a high pipe pressure rating, preferably high enough to withstand a detonation.

The nominal H2-air detonation peak pressure is about 10-20 times the initial pressure, but there are also possible reflected pressures, a comfortable margin is needed to withstand shock wave pressures above the nominal detonation peak pressure. It’s possible for reflected pressures to get a little higher, but these generally remain within 20X. If a pipe is at atmospheric pressure, 300 psig will result in 20X the pressure, so that is the basis for the 1200 psig pipe having sufficient margin. 

FAQ Category
Submission Year
2024
Month
05

Static Charge - Piping

When flowing high purity hydrogen through an insulative tube, could a charge develop in the tube? The application in question is a system for filling stratospheric balloons with hydrogen lift gas. The system will be flowing > 99.2% hydrogen through a polyethylene film (insulative) pipe. Would a significant charge develop solely due to the gas flow? Does this apply both to conductive and non-conductive piping?

The HSP discourages the use of this type of piping for hydrogen despite the low likelihood of ignition within the pipe itself. The polyethylene film can indeed develop a charge and, depending on the film thickness and substrate wall material, will eventually produce an electrostatic discharge. Since the nominal hydrogen concentration is so high (and assuming the purge-in and purge-out procedures preclude flammable mixture formation), these electrostatic discharges should not produce an ignition in the pipe itself. However, besides this type of pipe not being a good practice for flammable gas flow, there is concern about an electrostatic discharge possibly occurring at the pipe exit and at any junctions between pipe sections. 

One particularly energetic type of electrostatic discharge is a propagating brush discharge, which occurs when a thin film of an insulating material with a high charge retention capacity is attached to a conductive material. The propagating brush discharge occurs over a large section of the insulating film and might extend beyond the pipe exit if the polyethylene film extends to the exit. If the hydrogen is flowing into an air atmosphere, an electrostatic discharge at the pipe exit could ignite the flammable mixture formed near the exit. If the pipe wall itself is combustible, a local ignition from leaking hydrogen could lead to pipe degradation and eventual containment failure of the pipe.

As a good practice, hydrogen piping should be conductive and bonded/grounded to avoid electrostatic charge generation from a variety of mechanisms including atmospheric discharges. The hydrogen gas itself should not develop an electrostatic charge during pipe flow, but the gas flow can entrain pipe scale or other contaminant particulates that develop electrostatic charges that can ignite the hydrogen vented into air. Autoignition during emergency venting of hydrogen at pressures greater than 200 bar can occur due to shock wave compression heating near the vent exit, but it’s doubtful this would occur during controlled filling of balloons because of the lower velocities expected in that application.

FAQ Category
Submission Year
2024
Month
05

Pressure Testing

Are there concerns about residual ethylene or propylene glycol left in hydrogen gas piping from pressure testing the line in freezing climates (prior to service)?

The HSP recommends against the use of glycols for pressure tests due to the difficulty of adequately removing all glycol that might be left in a system after a hydrotest. The HSP recommends a pneumatic test at 110% of the system maximum allowable working pressure (MAWP), which is acceptable by code. Due to an increased danger with pneumatics vs hydrotesting, establish a pressure test zone for personnel in the area. 


Several concerns with glycols are: 1) Freezing in a liquid hydrogen   system that could lead to safety issues such as blockage of lines and instrumentation. There could be dead legs or low spots that cannot be emptied or cleaned easily leaving enough to freeze important components such as small gauge lines, vent stacks, and relief devices. 2) Freezing at cold ambient temperatures or within dispenser piping that chills the dispensed gas can also lead to blockage of lines and instrumentation. 3) Off-spec hydrogen if not well cleaned from the lines, vessels, instrumentation, and dead legs of a system. Glycol can interact with materials such as aluminum and lead to pitting and corrosion.

Another concern for glycol solutions is that they are flammable. A leak generated during pressure testing could generate a spray that is readily ignitable by nearby ignition sources. For automatic sprinkler antifreeze solutions, the requirement is to use UL-listed solutions that have undergone flammability testing. with the pressures used in applicable systems. These pressures are at least an order-of-magnitude lower than what is typically used for hydrogen piping. This safety concern can be mitigated by preventing personnel and ignition sources from being near the piping when tested.

As a general rule, pneumatic testing is preferred over hydrostatic, especially for systems with complex piping geometry, as long as proper precautions are taken for the Pressure-Volume (PV) energy. The HSP recommends using a pneumatic test at 1.1 times the design pressure using a clean, dry, inert gas such as nitrogen. This is a best practice for field testing where cleaning afterward is even more difficult. Helpful resources that describe precautions to take are: 1) UK HSE G4 Safety in pressure testing, says to (a) perform a hazard analysis considering stored energy, blast effects, and missile formation; (b) develop a written procedure; and (c) examine system prior to test. 2) ASME PCC-2, Repair of Pressure Equipment and Piping, says to limit stored energy in any one test loop to 271,000,000 J (200,000,000 ft-lb) (0.07 tons TNT). If the stored energy requirement can’t be met, barriers must be erected or separation distances in excess of 60 m (200 ft) must be used. The HSE document offers broad guidance, while the ASME document provides more specific information about precautions as a function of the stored energy.

 

FAQ Category
Submission Year
2024
Month
05

Leak Testing Pressure

What is the required pressure (if any) for leak checking newly assembled hydrogen piping systems? It is unclear what pressure is required when constructing a system, prior to initial operation, and the applicable code section seems to suggest exceeding the maximum allowable working pressure or at the very least reaching a pressure that will activate pressure relief. ASME B31.12 seems to be very specific regarding welded pipeline systems; how does it apply to other types of connections from hydrogen fueling stations like double ferrule compression fittings?

The Panel recommends performing a pressure test at 110% of design pressure. This requirement should be applied to all systems regardless of construction type since the intent is to ensure pressure integrity and proper installation. All fitting types have modes of failure during installation. For example, there are numerous examples where compression fittings have had ferrules installed incorrectly, tubing improperly inserted, and have been inadequately tightened. In addition, leak checking and pressure testing should always be done in accordance with the locally adopted piping code.  Examples include ASME B31.3 and the Pressure Equipment Directive. 

 
System pressure relief devices will usually need to be removed for the test and temporarily replaced with higher setpoint devices to protect the system during the pressure test. Also, consider a proportional acting relief device.  Piping systems do not require a pop-acting ASME relief valve that are used for pressure vessels since piping system relief devices are more likely to chatter. Chatter can lead to lower than intended flow rate and damage or failure of the valve to operate correctly.   
For high-pressure systems, pneumatic testing is almost exclusively done given the challenge of removing water from a hydro test from the system after the test. Although one might question the wisdom of pneumatically testing at such high pressures, precautions can be taken to ensure a safe test, such as requiring an exclusion zone during the testing.   
 

FAQ Category
Submission Year
2024
Month
05

Pipe Connections

Can compression fittings for 304 or 316 SS tubing that use compressive forces to swage the fitting on onto tubing be used? The fitting is made for up to three pieces. One concern is the potential for hydrogen embrittlement in the area around the joint compression as the pipe is under large stresses when the joint is made. There is a video on how this works at the link below, starting at ~ 2 min 20 secs. (437) The Lokring High Performance Connector System - YouTube

The HSP is not familiar with this particular fitting or its potential application in H2 service but can offer engineering judgment. Many similar compression-type swaged fittings are used in H2 service. These fittings must be used within the manufacturer recommendations for pressure, temperature, and fluid service. Deformation is also introduced into stainless steel tubing in other ways, such as creating bends, but these locations are not reported to be more vulnerable to failure in H2 service provided that they are within an acceptable range.   

This is probably 300-series stainless steels, particularly 316, that are resistant to hydrogen embrittlement under static stress, although cyclic stresses add the potential for hydrogen-assisted fatigue cracking. One area of caution when applying the fitting to 304 piping is the potential to form strain-induced martensite (phase with magnetic signature) in the stainless steel. The martensite phase is more susceptible to hydrogen embrittlement than the surrounding matrix, and a widely recognized best practice is to limit the formation of these phases with magnetic signature for stainless steels in hydrogen gas service.


As with all compression-style fittings, there is a significant risk of incorrect or incomplete installation. Examples include failure to install the ferrules, installation of the ferrules in the wrong order or backwards, incomplete insertion, and incomplete tightening to reach the proper swaging of the tubing to ensure the necessary grip at high pressure. Fittings should always be inspected, either visually or with appropriate tools, and pressure tested prior to putting into service.
 

FAQ Category
Submission Year
2024
Month
04

Cathodic Protection

The local AHJ has asked if any part of the system piping will be routed below ground and has requested details on required corrosion protection system, trenching, and backfill. They cite the following sections of NFPA2: 7.1.15.3.2 Contact with Earth. 7.1.15.3.2.1 Gas piping in contact with earth or other material that could corrode the piping shall be protected against corrosion in an approved manner. "55:7.1.17.2" 7.1.15.3.2.2 When cathodic protection is provided, it shall be in accordance with 7.1.18. "55:7.1.17.2.1" 7.1.15.3.3 Underground piping shall be installed on at least 6 in. (150 mm) of well-compacted bedding material. "30:27.6.5.1" 7.1.15.3.4 In areas subject to vehicle traffic, the pipe trench shall be deep enough to permit a cover of at least 18 in. (450 mm) of well-compacted backfill material and pavement. "30:27.6.5.2" 7.1.15.3.5 In paved areas where a minimum 2 in. (50 mm) of asphalt is used, backfill between the pipe and the asphalt shall be permitted to be reduced to 8 in. (200 mm) minimum. "30:27.6.5.3" The instrument, air and hydrogen lines are stainless steel and will be installed in a PVC sleeve. In the Panel’s experience, is this adequate cathodic protection for the lines?

The Panel considers two approaches to be acceptable. 

  1. Stainless steel (corrosion resistant) lines embedded in concrete. This keeps the piping out of direct contact with the earth and provides a degree of physical protection from activities such as digging. 
  2. Lines enclosed within a PVC sleeve. The PVC sleeve would usually be directly buried but could also be embedded in concrete for additional protection.
    Cathodic protection is also an available and acceptable means of corrosion protection for underground lines, particularly for carbon steel. Each installation should be evaluated for local hazards and soil conditions to develop a thorough corrosion protection system. 
     
FAQ Category
Submission Year
2024
Month
04

Storage Options

What is the best approach for buffer storage of large quantities of relatively low-pressure gaseous hydrogen (~50 - 500 psi) in used propane or natural gas infrastructure? Suggested approaches include 90,000-gallon industrial propane tanks (similar to https://www.transtechenergy.com/ngl-lpg-propane-butane-asme-storage-tan…) or using natural gas pipelines for hydrogen storage. While the use of natural gas pipelines for hydrogen storage has been a hot topic of late, there are concerns over quality of welds/construction and material compatibility issues when switching natural gas infrastructure over to 100% hydrogen. Does the Panel have recommendations regarding the safe use of these kinds of systems for hydrogen storage, and are there good resources to learn more about this? Does the Panel know of other low-cost gaseous hydrogen storage options that have been implemented successfully and safely?

Regarding the concept of introducing hydrogen gas into natural gas pipelines, this is indeed a hot topic and there are recent quantitative treatments of fatigue crack growth driven by pressure cycling and potentially accelerated by hydrogen.  Some analysis has shown that it can be acceptable to operate natural gas pipelines with a hydrogen blend.  However, this is highly dependent upon the pressure and wall stress.  Whereas low pressure distribution lines with low wall stress are more amenable, the higher pressures and wall stresses of major transportation pipelines may not be.  Deep cyclic stresses that might occur from using pipelines as storage  may also create additional issues since hydrogen can accelerate fatigue crack growth, especially for systems where both hydrogen and deep cycles were not anticipated in the original design.  Individual pipelines likely need to be evaluated based on their design and there is likely to be no single answer for this question of pipeline storage. 

    
For industrial propane tanks, the Panel needs more information about structural materials and their properties (including welds). All propane tanks are not built from the same materials or with the same construction techniques, so these tanks likely need to be evaluated on a case-by-case basis. Propane tanks are often built with techniques that leave potential internal features that are susceptible to the initiation of crack growth. In addition, and depending on the application, it’s likely that the cyclic pressure service will be significantly different for a tank in hydrogen service, particularly one that might be cycled deeply on a daily (or more frequent) basis. From the perspective of the low-pressure storage options, while it is tempting to repurpose old LPG vessels for hydrogen service, the Panel cautions against it due to the potential for hydrogen embrittlement in the steel/weld material. Also, a challenge with newer propane tank designs is that they are moving to thinner walls and higher strength steel, which is notably less resistant to embrittlement than older vessels, so counterintuitively, newer tanks might be less amenable to hydrogen than older tanks.   


Another concern for vessels in hydrogen service is the amount of non-circularity, or “peaking” of the longitudinal welds.  This is not as much of a concern for propane so is likely not to be part of a standard design specification. This manufacturing issue can have a severe effect on cyclic life and is well understood when designing and building high cyclic hydrogen vessels, but not propane. Besides the issue described above for the tank itself, there are similar potential embrittlement issues for PRVs, instrumentation, and other accessories on these tanks. Many incidents have been due to component failures in these accessories. 
In conclusion, propane vessels were not designed for H2 cyclic service. Almost by definition, the reason people want to use them is for storage. and that is likely to be over a wide pressure range. Fracture mechanics should be applied to all cyclic H2 service vessels, especially if they start from another service. Propane tank designs vary and unless a tank is specifically intended for H2, there is no guarantee of what might be used terms of materials and construction techniques.
 

FAQ Category
Submission Year
2024
Month
05

Venting System

Should a venting system be installed for the relief valves on backup cylinders of hydrogen gas in an outdoor storage/use area, as is done for the hydrogen venting system indoors?

Regarding cylinders, it is not necessary to capture the fuse-backed devices which are on the cylinder itself. However, all other relief devices and vent valves must exhaust from a vent system designed in accordance with CGA G-5.5. Also, note that NFPA 2-7.1.17 requires compliance with CGA G-5.5 regardless of storage quantity when the vent system is servicing pressure relief devices. Cylinders in storage that are capped and within an approved cylinder storage area do not require a vent system.

FAQ Category
Submission Year
2024
Month
04

Piping Compatibility

When generating hydrogen in a high-pressure catalytic reactor, what type of material should be used to prevent H2 embrittlement or corrosion?

The selection of a material is always at the discretion of the system designed and appropriate metallurgical experience knowledgeable about the process should be consulted as necessary.   316 stainless steel is one example of a material that is generally suitable for generation and containment of high-pressure hydrogen gas, but it is important to ensure stress levels in the piping and reactor structure are sufficiently low at the design pressure/temperature limits and within the allowable stress levels prescribed in ASME codes for pressure equipment and piping. As with any application, care must be taken in each specific application to address the required pressure, operating temperature, and potential contaminants, all of which could affect the material. 

FAQ Category
Submission Year
2024
Month
05
Subscribe to Piping
We are professional and reliable provider since we offer customers the most powerful and beautiful themes. Besides, we always catch the latest technology and adapt to follow world’s new trends to deliver the best themes to the market.

Contact info

We are the leaders in the building industries and factories. We're word wide. We never give up on the challenges.

Recent Posts