Should a venting system be installed for the relief valves on backup cylinders of hydrogen gas in an outdoor storage/use area, as is done for the hydrogen venting system indoors?

Regarding cylinders, it is not necessary to capture the fuse-backed devices which are on the cylinder itself. However, all other relief devices and vent valves must exhaust from a vent system designed in accordance with CGA G-5.5. Also, note that NFPA 2-7.1.17 requires compliance with CGA G-5.5 regardless of storage quantity when the vent system is servicing pressure relief devices. Cylinders in storage that are capped and within an approved cylinder storage area do not require a vent system.

Category
System Design
Keywords
System Design
Vent
Piping
Pressure Relief Device
Submission Year
2024