Hydrogen Furnace Leak

First Name
Andy
Last Name
Piatt

The hydrogen feed system for the furnaces inside a pit furnace developed a leak. The leak was on the hydrogen dryer inside a shack attached to a building. The leak vented 200 psig hydrogen into the shack. The hydrogen low-pressure alarm sounded. No furnace operators were present at the time. An estimated 10,000 standard cubic feet of hydrogen vented. T

Hydrogen Make Up Compressor Piping Hole

First Name
Andy
Last Name
Piatt

During inspection of a hydrogen make-up compressor, it was discovered that a 1/4” stainless steel screw and nut that mounted a temperature gauge to a stainless steel pipe was resting against the side of a schedule 160 high-pressure hydrogen pipe. Constant vibration of the process equipment had caused the bolt to rub a hole in the high-pressure suction piping, resulting in the release of make-up hydrogen. The pipe was out of sight, and the problem was identified by an employee who heard the whistling sound of escaping hydrogen. The compressor was taken offline and depressurized.

Deviation from Work Plan Results in Cutting Pipe Prior to Second Explosive Gas Test

First Name
Andy
Last Name
Piatt

A demolition technician noted an elevated combustible gas lower explosive limit (LEL) on a pipe that was being tested prior to cutting (No. 2 pipe). The No. 2 pipe was one of four pipes being tested. The other three pipes tested less than detectable for combustible hydrogen gas. Testing involves tapping the pipe and connecting the pipe to an Explosive Gas Detector via a tube. When an elevated LEL is identified, the pipe is allowed to vent and then retested prior to cutting. After tapping the No. 2 pipe, the work crew left the pipe open to vent and departed the area for the end of shift.

Degradation of Safety-Significant Valve

First Name
Andy
Last Name
Piatt

The valve stem for a funnel valve to a solution neutralization tank was found to be separated from the body of the valve. This valve is used for purging hydrogen gas from the vessel. The functional classification of this valve is safety-significant. The "as-found" condition of the affected valve prevented the valve from performing its intended design function.

Hydrogen Purge Frequency Exceeded in Vessel

First Name
Andy
Last Name
Piatt

An operator went to purge a process tank per standard operating procedure. The operator reviewed the previous shift's purge time and determined the next required purge time. The operator found that the tank had been purged earlier than expected on the previous shift. Because the earlier purge time was not recognized, the 12-hour purge frequency was exceeded.

Deficiency Discovered in Hydrogen Sensor Application

First Name
Andy
Last Name
Piatt

A deficiency was discovered in the application of a hydrogen sensor in the Rotary Mode Core Sampling (RMCS) portable exhauster. The sensor is installed in the flow stream of the exhauster designed to be used with a RMCS truck for core sampling of watch list tanks, and is part of the flammable gas detector system. During the previous week, a quarterly calibration of the sensor, per maintenance procedure, was attempted by Characterization Project Operations (CPO) technicians. Ambient temperatures during the sensor calibration were approximately 20 to 30 degrees F.

Concern Identified Regarding Installation and Commissioning of Compressed Gas Systems

First Name
Andy
Last Name
Piatt

While research staff were working in a lab, a staff member opened the primary valve to a 0.2" (1500 psi) hydrogen gas line connected to a manifold supplying instruments in the lab. Upon opening the valve, the hydrogen gas line failed at a fitting on the switching manifold, releasing a small amount of hydrogen gas. The staff member closed the valve immediately, then inspected the gas line and found the front ferrule (of the compression-style fitting) to be missing. There were no injuries or damage to equipment.

Failure of Rotameter Causes LFL Analyzer Low Sample Flow

First Name
Andy
Last Name
Piatt

A control room received a tank lower flammability limit (LFL) analyzer low sample flow alarm. The control room operator initiated the appropriate alarm response procedure and the facility entered limiting conditions of operation. At the time of the alarm, the facility was experiencing severe weather and the field operator was unable to investigate the alarm in the field. After the severe weather cleared, the field operator investigated the alarm and found the sample flow to be low and out-of-limits.

Temperature Excursion in Environmental Chamber Results in Small Fire

First Name
Andy
Last Name
Piatt

A temperature excursion occurred in a sealed environmental chamber during a 0°C ambient temperature test. An elevated temperature in the chamber resulted in a small fire that was confined to the environmental chamber. Visual observation indicated no damage to nearby equipment, including nearby computer cables.

Hydrogen Alarm Activates in Processing Facility

First Name
Andy
Last Name
Piatt

A process area alarm activated. The alarm was caused by an instrument channel located above a reaction vessel off-gas system final HEPA filter canister, which indicated 25% of the lower explosive limit (LEL) for hydrogen. Since the only source of hydrogen is from the reaction vessel during the reaction of sodium with concentrated sodium hydroxide, the immediate actions were to shutdown the reaction process and place the facility in a safe condition.

Subscribe to None