If the concentration of hydrogen is less than the Lower Flammability Limit (LFL) of 4% in an inert gas, it is unlikely that a leak of this gas mix will form a flammable mixture as it dilutes into air. For example, industry uses ‘forming gas’, a mixture of 4 to 5% H2 in nitrogen, as an oxide reducing agent in materials processing furnaces and soldering operations. This mixture can also be used…

Because hydrogen leaks frequently ignite, and because about half the time the ignition source is not identified, when evaluating hazards with hydrogen leaks, many people just assume the leak will be ignited. Note that consideration needs to be made for what may happen with immediate ignition (jet fire) and what may happen with delayed ignition (explosion). 

It is still important to…

Category: Miscellaneous

Sprinkler systems and other fire suppression means are prescribed per building and fire codes to limit fire spread to other materials. In the case of a hydrogen leak and fire, it is best practice to isolate the hydrogen source, and let any residual hydrogen gas burn out. Even if the initial fire is extinguished, additional leaking hydrogen may accumulate and ignite with the potential for an…

In general, indoor storage should be limited and the use of hydrogen indoors should be the least necessary. Look to store flammable gases outdoors in dedicated protected area when practicable. Check to see what adopted building and fire codes in your jurisdiction say. NFPA 2, Hydrogen Technology Code, Sections 6.4.1 and 16.3 prescribe requirements to limit hydrogen storage and use in…

Category: Miscellaneous

Outside storage is generally considered safer and is required for large amounts of gas. Stationary storage should be located outside at a safe distance from structures and ventilation intakes, and protected from vehicle impact. 

Hydrogen storage separation distance requirements are typically based on the quantity and pressure of the hydrogen or the piping diameter, depending on the…

The answer is dependent upon the nature of the system and a hazard assessment which evaluates a balance of risk. 

Keeping the hydrogen in the vessel is better so the hydrogen release does not compound the original hazard. Large flowrates from vessels can create significant risk of vapor cloud explosion, jet explosion, or radiation exposure. Vent systems can also fail from poor…

Purging is not recommended as a continuous part of vent stack operation. However, maintenance activity is a transient event and it’s prudent and recommended to purge a vent system prior to performing maintenance. It’s always possible that hydrogen could be leaking internally from a valve or other component and therefore create a hazard. Of particular note, care must be taken that proper…

Category: Miscellaneous

There are many potential sources of delayed ignition. Hydrogen is easily ignited, and the larger the cloud, the more likely it is for it to find an ignition source. The cloud itself may serve as an ignition source as the force of the gas release may cause dust or other contaminants to mix in the air creating a static charge which ignites the hydrogen. Similarly, the force of the release can…

We are not aware of a study for blended NG/H2. However, for high concentrations of NG, the vent system should be similar to NG, which still recommends a vent system as NG is less dense than air. For nearly pure hydrogen the recommendations of this presentation are in effect.

Category:

We would not open the vent system to inspect the internal piping without a good reason.

It is recommended to check for water in the vent stack trap

  1. At startup and daily during startup.
  2. On LH2 tank system, every delivery
  3. After the 1st rainstorm after a system is installed
  4. LH2 vent stacks after establishing the baseline above
    1. After every large…