CGA G-5.5 states: All vent stacks shall be grounded and meet the requirements of NFPA 70, National Electrical Code, for integrity and system design and also references NFPA 77, Recommended Practice on Static Electricity, and NFPA 780, Standard for the Installation of Lightning Protection Systems. 

For lightening refer to NFPA 780 and for grounding of the Hydrogen equipment, refer to…

Category: Hazards Analysis
Keywords: Vent Stack, Requirements, Grounding, NFPA

AICHE ELA253 CHS ” Introduction to Hydrogen Safety for First Responders” is a good reference and discusses both LH2 and GH2. LH2 fires are very unusual. LH2 releases usually are GH2 so the fires at either ambient for low flow or the GH2 is a cryo temperature for high flow. Fires from LH2 tanks ignite less frequently than GH2 high-velocity releases. The colder the gas the less potential for…

Category: Hazards Analysis
Keywords: First Responders, Safety, LH2, GH2, Guidelines, Fire Protection

There are numerous models that can be used to assess the consequence and risk of leaks and releases.
One such model is HYRAM which is publicly available from Sandia and the US DOE.

Category: Hazards Analysis
Keywords: Leak, Simulation Models, HYRAM, Risk Assessment

Emergency response procedures must be developed for each system based on its design. The
procedures generally include steps to clear personnel from the immediate area, isolate the hydrogen,
shut down the equipment, contact local responders, and protect surrounding equipment/structures until
the hazard is mitigated or the incident is over.

Category: Hazards Analysis
Keywords: Emergency Response

Absolutely. Vent systems will experience a variety of transient conditions of pressure, temperature, and thrust load, so stress analysis to anticipate the strength and flexibility needed are important for safe design. These issues are often overlooked and only become an issue when they are called upon to operate in emergencies. 

It is a best practice to include the vent system in…

Category: Hazards Analysis
Keywords: Vent, Piping, Stress Analysis , Vent System, Hazards Analysis

There are many potential sources of delayed ignition. Hydrogen is easily ignited, and the larger the cloud, the more likely it is for it to find an ignition source. The cloud itself may serve as an ignition source as the force of the gas release may cause dust or other contaminants to mix in the air creating a static charge which ignites the hydrogen. Similarly, the force of the release can…

Category: Hazards Analysis
Keywords: Delayed Ignition, Hazards, Hazards Analysis, Codes

The answer is dependent upon the nature of the system and a hazard assessment which evaluates a balance of risk. 

Keeping the hydrogen in the vessel is better so the hydrogen release does not compound the original hazard. Large flowrates from vessels can create significant risk of vapor cloud explosion, jet explosion, or radiation exposure. Vent systems can also fail from poor…

Category: Hazards Analysis
Keywords: Hazards Analysis, Pressure Vessel, TPRD, Vent System

Outside storage is generally considered safer and is required for large amounts of gas. Stationary storage should be located outside at a safe distance from structures and ventilation intakes, and protected from vehicle impact. 

Hydrogen storage separation distance requirements are typically based on the quantity and pressure of the hydrogen or the piping diameter, depending on the…

Category: Hazards Analysis
Keywords: Safety, Outdoors, Storage, Requirements, NFPA 2

Sprinkler systems and other fire suppression means are prescribed per building and fire codes to limit fire spread to other materials. In the case of a hydrogen leak and fire, it is best practice to isolate the hydrogen source, and let any residual hydrogen gas burn out. Even if the initial fire is extinguished, additional leaking hydrogen may accumulate and ignite with the potential for an…

Category: Hazards Analysis
Keywords: Fire Protection, Codes, Leak, Explosion