Is there a hazard using a 4/96% hydrogen/nitrogen blend if it is released to the air?

If the concentration of hydrogen is less than the Lower Flammability Limit (LFL) of 4% in an inert gas, it is unlikely that a leak of this gas mix will form a flammable mixture as it dilutes into air. For example, industry uses ‘forming gas’, a mixture of 4 to 5% H2 in nitrogen, as an oxide reducing agent in materials processing furnaces and soldering operations. This mixture can also be used in conjunction with a hydrogen detector for leak testing gaseous hydrogen equipment.

FAQ Category
Submission Year
2023
Month
09

Hydrogen Detector Standards

Is there a standard for sensors (detection) for mobile applications such as hydrogen road transportation, similar to the ISO 26142:2010 standard for stationary applications?

The Panel is not aware of any standard for hydrogen detectors for onboard vehicle applications. Some information is available in the SAE Technical Information Report: TIR J3089 Characterization of On-Board Vehicular Hydrogen Sensors, which was published in 2018.

FAQ Category
FAQ Keyword
Submission Year
2024
Month
05

Sensors

What guidance is available for implementing hydrogen flame detection using IR cameras? Specifically, what are the recommendations for filters? What about camera characteristics, maximum distance, and so forth?

One pertinent reference is a Sandia National Laboratories paper by Schefer et al: Spatial and radiative properties of an open-flame hydrogen plume, Intl J. Hydrogen Energy, 31 (2006): 1332-1340. Information on this and other similar papers are available at https://h2tools.org/bibliography. Further information can probably be obtained from the author of this paper and other papers reporting hydrogen flame spectral distributions. Of course, hydrogen flame sensor manufacturers also have such data and should be consulted.  Specifications on these sensors should provide useful data.

FAQ Category
FAQ Keyword
Submission Year
2024
Month
05

Ultraviolet (UV) Infrared (IR) Detectors

With IR/UV detectors as commonly used in hydrogen vehicle station forecourt applications, what would be the expected size of any leaks and resultant jet fires? What about interference and the tendency for existing technologies to be shut down in situations where there could be false positives from background radiation, lightning, and sun reflection off a vehicle mirrors?

There are many manufacturers of multiple  types of flame detectors and it’s best to seek their input for the advantages of different types for specific applications. Regarding flame detector technology, UV detectors have been prone to false alarms from outside sources such as sunlight, lightning, and welding/cutting torches. The newer triple-IR detectors that are specifically designed and tested for hydrogen flames have been shown to be effective. These detectors are currently in use at many hydrogen systems for detecting both hydrocarbon and hydrogen flames. Also, flame detection will only detect a leak once the hydrogen is ignited.  It is difficult to assess the minimum leak size without specific testing at known hydrogen pressure and the distance of the detector from the leak

FAQ Category
Submission Year
2024
Month
05

Sensors

What guidance is available for addressing issues with LEL sensor reliability when commissioning a regenerative thermal oxidizer? The project in question uses hydrogen gas along with some volatile organic compounds mixed at approximately 1-2% by volume in air. The flow is under slight vacuum at -8 water column in an 8” pipe. The sensor needs to be able to detect at least two levels of hydrogen concentration (1.5% and 3.5%) to ensure the LEL is not exceeded. The project also wants to attach an alarm to the output from the sensor. The service is continuous monitoring, and a sensor that can last at least 6 months is desired. The project may consider a second system to enable change-out of sensors while running.

The answer will depend on if it is only H2 measured or if VOCs are also included. The type of gas sensor may change since many detectors are limited to flammable gases. To provide feedback, the Panel would require more details on the sensors being used on the project and the failure modes. There are concerns about allowing hydrogen concentrations as large as 3.5% for the high level alarm. Since VOCs are mixed with the hydrogen, the mixture lower flammability limit is probably slightly less than 4%. A typical practice would use 25% of the LFL, or 1% hydrogen), for alarm, not 1.5% to 3.5%. The vacuum may be an issue, as normally these are operated at atmospheric pressure. Engineering discussions with vendors and research would be needed to assure VOCs are not an issue and the vacuum is suitable. Staff at the National Renewable Energy Laboratory have experience with a range of sensors and may be able to help, particularly if the failure mode with the current sensors is known.  As always, experienced sensor manufacturers should also be consulted for assistance.

FAQ Category
FAQ Keyword
Submission Year
2024
Month
05