Operators in a powdered metals production facility heard a hissing noise near one of the plant furnaces and determined that it was a gas leak in the trench below the furnaces. The trench carried hydrogen, nitrogen, and cooling water runoff pipes as well as a vent pipe for the furnaces.

Maintenance personnel presumed that the leak was nonflammable nitrogen because there had recently been a nitrogen piping leak elsewhere in the plant. Using the plant's overhead crane, they removed some of the heavy trench covers. They determined that the leak was in an area that the crane could not reach, so they brought in a forklift with a chain to remove the trench covers in that area.

Eyewitnesses stated that as the first trench cover was wrenched from its position by the forklift view more

A gas mixture cylinder was connected to a Fourier Transform Infrared (FTIR) Spectrometer to purge residual carbon dioxide and water vapor. A staff member was preparing to use the FTIR instrument. Prior to use of the instrument, it must be purged with dry nitrogen to remove residual carbon dioxide and water vapor. When the gas mixture reached the instrument's globar (resistively heated ceramic) heat source, a localized explosion occurred. No injuries resulted from the explosion but the spectrometer housing was heavily damaged. The internal components, including the optics and computer hardware, appeared to be in good shape.

A mixture of hydrogen and nitrogen was inadvertently connected for the purging rather than dry nitrogen. The staff member, even though an expert in the view more

An explosion occurred in a 90-ton-per-day incinerator at a municipal refuse incineration facility. Three workers were seriously burned by high-temperature gas that spouted from the inspection door, and one of them died 10 days later. The accident happened during inspection and repair of the furnace ash chute damper. The workers injected water to remove some blockage, and the water reacted with incinerated aluminum ash to form hydrogen, which caused the explosion.

Workers noticed that the post-combustion zone was full of ash and the ash pusher was not working properly, so they tried to remove the ash from the inspection door with a shovel. They discovered a solid layer of "clinker", which is formed by solidification of molten material such as aluminum. The explosion view more

A hydrogen explosion and fire occurred in the benzene unit of a styrene plant in a large petrochemical complex. The unit was being restarted following a scheduled maintenance shutdown. The explosion followed the release of about 30 kilograms of 700-psig hydrogen gas from a burst flange into a compressor shed. Two men were killed and two others were injured. If it had not been a holiday, the death toll and injuries would probably have been much worse.

The operators were bringing the plant online and increasing the hydrogen circulation pressure. About 10-15 seconds before the explosion, they heard a pop and then a loud hiss of pressure being released within the compressor shed. Witnesses reported seeing a white flash and then a large fireball. The fires burned out in 2-3 minutes, view more

A researcher was using numerous compressed gases in his lab. To facilitate reconfiguring his experimental apparatus, he installed "quick-disconnect" fittings on flexible tubing connected to his compressed gas cylinders/regulators. He also fitted all of the equipment that needed gas with complementary "quick-disconnect" fittings.

The day of the incident, he needed to purge his IR spectrometer with nitrogen as the element heated up. He mistakenly attached the "quick-disconnect" fitting from a cylinder of 10% nitrogen and 90% hydrogen to the "quick-disconnect" fitting on his spectrometer. As soon as the gas started flowing and he switched on the element, the instrument exploded, completely destroying a $6,000 piece of equipment. Only minor view more

An accident occurred during setup for a popular hydrogen-oxygen balloon science demonstration at a local public school. The demonstrator suffered painful second-degree burns to his right forearm and was taken to the hospital. The paramedics feared that grave respiratory damage (due to flame inhalation) might have occurred.

The demonstrator had transported 15 helium-quality balloons, pre-filled with a hydrogen-oxygen mixture, in a large, black, polyethylene garbage bag. During the setup, he opened the bag to remove a single balloon for stringing and floating. Without warning, the entire bag of balloons detonated violently. Fortunately, the incident occurred an hour prior to the program and no one else was near. It was also fortunate that only a small box caught fire and none of view more

During the early morning hours on a Tuesday, a university support staff member was preparing for an off-campus community outreach program for high-school-age students in the community. One of the program demonstrations was to show students the reaction energy and properties of the hydrogen + oxygen = water chemical reaction. It was a demonstration that the professor and the staff member overseeing the program had done for over 15 years with no incidents ever occurring.

To prepare for the demonstration, eight balloons were filled, four with pure hydrogen and four with the proper combination of hydrogen and oxygen. The balloons were placed into a larger plastic garbage bag and carried outside to a university-owned SUV located next to the building's loading dock. The bag of view more

A fatal accident took place at an onshore processing facility for slop water from the offshore petroleum industry.

Drilling fluids, or mud, are typically oil-water emulsions consisting of base oil (continuous phase), water (dispersed phase), and emulsifying agents. Used drilling mud, or slop, is mud enriched with water and rock cuttings from drilling --- typically 60-80% water, 10-20% emulated base oil, and 10-20% rock cuttings. The used drilling fluids are collected in slop tanks on oil platforms and later shipped to onshore facilities for further processing.

On the day of the accident, two operators were trying to remove the lid from a manhole on top of a 1600-cubic meter storage tank. However, they were not able to unscrew the rusted bolts holding the lid in place, and view more

A fueler drove away without disconnecting the fueling hose from the vehicle. The breakaway did not open and the receptacle fitting sheared off the vehicle. Subsequent testing of the breakaway showed that the breakaway operated at 210 lbs, which was above the design value of 133 lbs. The hydrogen contained in the hose between the dispenser shutoff valve and the vehicle check valve was released.

An explosion occurred within the hydrogen processing system of a chemical plant that produces sodium chlorate for bleaching pulp and paper. The chemical process utilizes electrolytic cells and is pH-dependent. Hydrogen is produced as a byproduct and is utilized as a fuel.

At the time of the incident, the plant was at an abnormal operating level of 25% capacity. A non-routine maintenance operation to repair high-pH liquid piping was in progress. To assist, operations personnel rerouted the high-pH liquid stream to the plant sump. However, in doing this, the liquid eventually made its way back into the electrolytic process by design. Ultimately this created the root cause of the explosive condition in that the pH of the electrolytic process increased faster than the computer- view more