Potential Un-reviewed Safety Question Due to Liquid Hydrogen Tank Installation

First Name
Andy
Last Name
Piatt

Installation of a 9000-gallon liquid hydrogen storage tank by a lessee at a building has not been evaluated for effect on the Safety Authorization Basis (SAB) of nearby facilities.

During review of an Emergency Management Hazard Assessment document, a reviewer questioned whether the SAB of nearby facilities had been reviewed for the effect of the installed 9000-gallon liquid hydrogen tank. Reviews by the facility management and facility safety personnel confirmed the evaluations have not been performed.

Pressure Reducing Clamp Removal Mishap

First Name
Andy
Last Name
Piatt

On a given day personnel were removing a blind hub that had been used to temporarily isolate a portion of a gaseous hydrogen system. As a result of a sudden release of 2,800 psig gaseous nitrogen, sand and debris kicked up from the concrete pad and caused minor injury to two technicians.

During the investigation, it was found that:

Incorrect Check Valve Installation

First Name
Andy
Last Name
Piatt

The contractor was replacing a needle valve and a check valve on the nitrogen purge line to the dispenser because of a small leak at the connection between the needle valve and the check valve. On reinstalling the valves, the contractor installed the check valve backwards, causing the pressure disk in the regulator to fail, venting about 1000 psig hydrogen into the air for about 10 seconds. This was found during testing of the contractor's work before the system was returned to normal service.

Fuel Cell Catalyst Fire

First Name
Andy
Last Name
Piatt

A student cleaned catalyst that was being used for a fuel cell membrane electrode assembly from a spatula. He then placed the contaminated paper towel into a waste container that contained other waste that was wet with alcohol. The alcohol reacted with the catalyst, igniting a fire within the waste container. The fire was extinguished with a beaker of water.

Hydrogen Reformer Tubes Ruptured during Startup

First Name
Andy
Last Name
Piatt

A hydrogen reformer furnace at a refinery was shutdown for maintenance to remove and cap the inlet and outlet headers of some radiant tubes that had previously developed hot spots and been isolated by externally pinching them off at the inlet. A decision was made to leave steam in the steam-generating circuit during this maintenance operation to prevent freezing. After maintenance was complete, the startup procedure required the furnace to be first heated up to 350°C (662°F) prior to introducing 4136 kPa (600 psig) steam into the radiant tubes.

Hydrogen Fueling Dispenser Nozzle Detached

First Name
Andy
Last Name
Piatt

The hydrogen fueling dispenser nozzle could not be completely disconnected from the vehicle after refueling. It was finally disconnected after trying several times. The cover of the nozzle interfered with the disconnection operation. No malfunction of the nozzle was found. It can be easily disconnected when it is withdrawn along its axis. Sometimes misalignment occurred due to the weight of the dispenser hose.

Leak in Liquid Hydrogen Pump Causes Explosion/Fire at Hydrogen Transfilling/Pumping System

First Name
Andy
Last Name
Piatt

A leaking liquid hydrogen cryogenic pump shaft during the process of filling a gaseous tube delivery trailer to 2400 psi at a liquid hydrogen transfilling location caused a series of explosions and a fire. After approximately 30 minutes of filling, the operator heard a single loud explosion and then saw flames and ripples from heat generation near the ground in the hydrogen fill area. The operator quickly actuated the emergency alarm system that shut down the cryogenic pump and closed the air-actuated valves on the cryogenic pump supply line.

Hydrogen Gas Explosion in Municipal Refuse Incineration Facility

First Name
Andy
Last Name
Piatt

An explosion occurred in a 90-ton-per-day incinerator at a municipal refuse incineration facility. Three workers were seriously burned by high-temperature gas that spouted from the inspection door, and one of them died 10 days later. The accident happened during inspection and repair of the furnace ash chute damper. The workers injected water to remove some blockage, and the water reacted with incinerated aluminum ash to form hydrogen, which caused the explosion.