A cryogenic hydrogen laboratory had a power outage. The cryogenic hydrogen storage was no longer being cooled, therefore temperatures and pressures within the storage system started rising. There were several relief devices on the system, one with a set point of 150 psi (approximately 1 MPa) and a second at a set point of 165 psi (1.1 MPa). The system was monitored by site personnel so that when the hydrogen pressure increased to 120 psi (approximately 0.5 MPa), a manual vent was opened. However, the manual vent rate was not able to control the rising pressure.