Explosion in a Fertilizers Plant
The vent occurred in the ammonia production unit. A minor leak had been detected in a flange on the piping of the ammonia synthesis loop (operating at 250 bar). The company called a specialized external contractor to perform an on-stream repair of the valve. This solution was chosen because of for the limited extents of the leakage and the economic costs and efforts associated to a shut-down of a very complex system. The on-stream repair consisted in: (1) fabrication of a special bracket in two parts adapted to the dimensions of the flange of the valve, and (2): injection of filling material in the bracket around the flange (the material had to be injected at a pressure higher than the operating pressure inside the pipe). During the repair some stud bolts broke causing the escape of a jet of a gaseous mixture of unknown amount of hydrogen and nitrogen at 250 bars. The escaping mixture exploded, killing 2 workers and damaging the valves and the piping.
Event Date
February 23, 1989
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
Immediate cause was the failure of a flange followed by the release of a nitrogen-hydrogen mixture.The investigation revealed that two causes have probably contributed to the accident: (1): the flange stud-bolts of the valve have been replaced by others made of a material not equivalent to the one originally specified;(2): the maintenance company performing the repair have not taken into account the overpressure on the stud-bolts due to the injection of the filling material in the bracket. Therefore the root cause could be identified in the lack of a proper risk assessment of the repairing operation.
Facility Information
Application Type
Application
Specific Application Supply Chain Stage
Components Involved
flange, bolt, ammonia synthesis loop, valve, bracket
Storage/Process Medium
Location Type
Location description
Industrial Area
Operational Condition
Pre-event Summary
Following the detection of a small leak repairing works had been subcontracted, to be performed while the plant continued its operation.
Currency
Property Loss (onsite)
1451027
Lessons Learned
Lessons Learned
After the accident, the following measures were established: - compilation of written maintenance procedures with emphasis on safety issues; - establishment of the sequence of operations to be followed during repair of such valves.
Event Nature
Emergency Action
After the explosion, the ammonia production unit was shut-down.No off-site emergency measures were necessary.
Release Type
Release Substance
Release Pressure (bar)
250.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
Source Category
References
References
Event description in European database eMARS
https://emars.jrc.ec.europa.eu/en/emars/accident/view/81b0a851-01f8-620…
(accessed September 2020)
Event description in the French database ARIA
https://www.aria.developpement-durable.gouv.fr/accident/176/
(accessed October 2020)