The Panel recommends performing a pressure test at 110% of design pressure. This requirement should be applied to all systems regardless of construction type since the intent is to ensure pressure integrity and proper installation. All fitting types have modes of failure during installation. For example, there are numerous examples where compression fittings have had ferrules installed…

Category: Piping
Category:
Keywords:

In the case of fuel-rich mixtures like those in the question, the heat of combustion for the mixture should be calculated on the basis of the oxygen content of the mixture. The heat of combustion per mole oxygen is twice the heat of combustion per mole hydrogen, i.e., it is 286*2 kJ per mole O2. You should be able to do the calculations based on this reply.

Category: Properties

I am communicating with a company that is exploring this technology for an application involving a mixture of flammable gases, including hydrogen.

Category: Explosions

Regarding cylinders, it is not necessary to capture the fuse-backed devices which are on the cylinder itself. However, all other relief devices and vent valves must exhaust from a vent system designed in accordance with CGA G-5.5. Also, note that NFPA 2-7.1.17 requires compliance with CGA G-5.5 regardless of storage quantity when the vent system is servicing pressure relief devices. Cylinders…

Category: System Design

The vent system for the excess hydrogen should be vented in accordance with NFPA 2 and CGA G-5.4 and G-5.5. The oxygen also must be vented safely and should be in accordance with NFPA and CGA G-4.4. 


Please be extremely cautious with compressing hydrogen. NEC/NFPA 70 and its Articles 500/505 address electrical equipment in flammable atmospheres. Please also consider the…

Category: System Design

The British Standards Institute (BSI) has published BS ISO 22734:2019, a British nationalized version of the packaged water electrolyzer safety certification standard. This standard can be used by a Notified Body (BSI is one of many operating in the UK and in Europe) to certify electrolyzer safety to established norms for this equipment. This standard addresses safety of containerized hydrogen…

Category: System Design

The regulations for electrical classification in Europe and a US jurisdiction such as California are significantly different and should not be assumed to be the same. Consultation with Authorities Having Jurisdiction or a Third- Party expert regarding the application of the US National Electric Code is advised. Some additional important points:


The HSP has concerns with the use of…

Category: System Design

There are no specific code resources that specifically cover hydrogen liquefaction plants, but they must be built to the general building, electrical, machinery, piping, and mechanical codes for process plants. Codes such as NFPA 2, Hydrogen Technologies Code, for installation and emergency response may also be used for reference. It may also be beneficial to break down the requirements into…

Category: System Design

Panel members have not encountered a device or area classification for ATEX approval within Canada. ATEX is a European Union directive and is not generally recognized within North American standards. The second link below references a UL similarity. https://news.nilfiskcfm.com/2017/03/atex-certification-applicable-north-america/;    https://www.ul.com/services/atex-certification-…