Hydrogen vent mesh code suggestions

Mesh at vent outlet can result in a fire at the vent. Is there any code suggesting that for hydrogen vent mesh?

Vent stacks must be designed for a fire at the outlet. The mesh is designed to ensure no blockage of the vent stack by animals/insects. 

Additionally, the mesh must be designed for pressure drop to ensure code-compliant back pressure on the relief devices.

FAQ Category
Submission Year
2024
Month
01

Testing – Explosion Prevention

Are there unique considerations when using foam and mesh technology to help prevent hydrogen explosions relative to other flammable gases?

No, but it is always necessary to determine the possibility of an adverse chemical reaction with the particular material being used for the mesh.

FAQ Category
Submission Year
2024
Month
04

Testing – Explosion Prevention

Has the Hydrogen Safety Panel had inquiries about metal mesh or polymer foam being used in composite or metal containers for hydrogen use as an explosion prevention system in accordance with NFPA 69?

The Panel has not received such inquiries. Section 14.2 of NFPA 69 Standard for Explosion Prevention Systems covers foam and mesh requirements. NFPA 69 states in 14.3.4 that the tests shall be conducted with a flammable gas/air mixture with a fundamental burning velocity representative of the burning velocities of flammable vapors expected in the intended applications.

FAQ Category
Submission Year
2024
Month
04