Skip to main content

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire in Hydrogenation Unit of a Monomer Production Plant
The fire was in a polyamide production chemical plant classified SEVESODuring maintenance of an isolated unit producing a polyamide monomer (LACTAME), a fire developed on the ground floor of the unit of hydrogenation of cyclo-dodecadiene (CDA). A fire detector on the unit triggered an alarm 4 min after the fire started and the station operator put the unit in safe conditions and alerted the firefighters of the site. The fire was controlled after a half an hour. The nitrogen inerting device of the reactors was put into service, it then presented malfunctions: difficulties of connection of the hose, leakage on the valve. There was no impact on the environment. Damage to the unit was noted (damaged valves, melting cables), it restarted 13 days later.The analysis of the accident by the plant operator showed that a sensor had failed to give the signal of low level in the CDA storage tank. The low level has allowed hydrogen into the production line, which was in stand-by. The hydrogen escaped from the manual valve at the bottom of the reactor finishing the process . This valve had already been found leaking a week before and tightened. In the presence of an unidentified ignition source, the leaked hydrogen ignited. The fire was further alimented by the opening of the valves of automatic degassing of the reactors, due fire damage. This opening caused the increase of the hydrogen supply of the unit. Late fire detection and too slow pressure drop in the decompression line were also aggravating factors.
Event Date
July 12, 2010
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
Immediate cause has been the failure of a low-level sensor, which has allowed the injection of hydrogen into the production line.
Facility Information
Application Type
Application
Specific Application Supply Chain Stage
Components Involved
polyamide monomer unit, hydrogenation of cyclododecadiene unit
Storage/Process Medium
Location Type
Location description
Industrial Area
Number of Fatalities
1
Lessons Learned
Lessons Learned
Unknown
Event Nature
Emergency Action
1.Shortly before 17h - fire develops on the ground floor of the hydrogenation unit of cyclododecadiene (CDA). 2.Four min after the fire started, a fire detector on the unit triggers an alarm and the station operator put the unit in safe conditions and alerted the firefighters of the site. 3.Half an hour later the fire is under control. 4.13 days later operations restart.
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
Source Category
References
References

ARIA data base
event no. 38732