Hydrogen Pipeline Leak Detected by Bubbling Water in Ditch (1059)

Early in the morning of (3:00 AM), the personnel on one of the companies on site reported a potential pipeline leak just south of the valve station. The potential leak was discovered due to bubbling water in the ditch. No visible hydrocarbon sheen was noted, indicating a probable non-hydrocarbon gas leak. Later in the morning, the personnel tested their area gas pipelines and determined that their company was not the source of the leak. Later on the same day, another company tested their pipelines and determined that their hydrogen pipeline was the source of the leak.

Weld Failure on Hydrogen Transmission Pipeline Causes Leak (1057)

Release from a welding of a hydrogen transmission pipeline At 12:45 pm the operation control centre (OCC) recognised that a customer flow and pressure dropped significantly. At 13:28 the OCC made the decision to close the upstream remote operated valve. At 15:00 the pipeline technician arrived on site and confirmed the breach in the pipeline. Additional pipeline operations technicians were deployed to isolate both manual block valve upstream and downstream of the incident site.

Hydrogen Release and Fire at Pipeline Meter Station During Winter Storm (1056)

A hydrogen release and subsequent fire occurred at meter station of a pipeline transporting hydrogen to a refinery. Local refinery emergency response team responded and secured the area. The pipeline was isolated, and the fire extinguished itself. During a winter storm, the area was experiencing abnormal freezing conditions and widespread power outages were occurring. As a result, third party hydrogen supply to the refinery was reduced. These upsets resulted in the need to export larger than normal flow rates on the hydrogen pipeline.

Explosion of a Storage Vessel in a Hydrogen Production Facility (1053)

This incident occurred at the hydrogen production and storage unit of (probably) a power plant using hydrogen as a coolant of the turbine-generator system. Hydrogen was produced probably by water electrolysis (the source does not say it) and stored in 6 steel tanks. One of the six hydrogen storage tanks exploded killing a staff member. The investigation determined that a mixing of hydrogen and oxygen occurred in the tank. The needle valve of the hydrogen and oxygen pressure regulator as jammed, and the oxygen leaked into the hydrogen main supply line and entered the hydrogen tank.

Fire in a Fertilizers Plant (1052)

a gas leakage (approximately 70% hydrogen, 21% nitrogen and the rest carbon monoxide and other impurities) occurred at the connection between a temperature measurement casing and a flange in the carbonization workshop cleaning tower. The leakage was reported to the plant leader, who issued the request to the workers to use iron cards and rubber plates to plug the leak. The operation failed and the leakage continued. At 17:00, at the request of the plant leader, the workers used a tire inner tube to wrap the leak.

Explosion in a Process Gases Line of a Fertilizers Production Plant (1051)

A gas release occurred in the building for the recirculation of processes gas. The gas was a mixture of hydrogen and nitrogen. It occurred at the outlet valve, during works aiming to replace it. This caused the creation of an explosive gas mixture and the surrounding spaces. The defective valve has been identified several years before, its poor design and ageing caused the gas leakage. The ignition took place with 9 minutes delay after initial leakage.

Explosion at a Pipeline of a Petrochemical Plant (1049)

A gas mixture (25% nitrogen, 73% of hydrogen, 2% methane) leaked, due to the ejection of the check valve from its connection with the inlet pipe. A large amount of the gas mixed with air and ignited, probably due to sparks generated by the ejected check hitting a metal pipe. It followed an explosion. Its pressure wave hit a gas pipeline causing its fracture and a fire. After about 1 hour and 30 minutes the fire was under control. The shockwave from the explosion caused a gas pipe at the back of the workshop to crack and leak, causing a large fire.

Explosion at a Methanation Reactor (1047)

The day before the incident, the outlet pipe connected to methanation reactor started leaking gas, which contains hydrogen. The leak was temporarily eliminated by a pressurised plug. On the day of the incident, the pipe leaked again, and the same plugging method was still used to stop the leak. This occurred without shutting down the unit and taking safety measures. Approximately one hour later, a sudden explosion occurred at the inlet line of the methanation reactor.

Pressure Vessel Failure in a Chemicals Plant (1045)

The vessel affected by the incident was a gas storage used for the desulfurisation process. The desulfurization gas had high hydrogen content. The vessels had cracks in the upper transverse fillet welds at the gas inlet which caused low stress brittle fractures. The cracks had been found during the maintenance, but not fixed. This eventually caused a gas release. Approximately 2.5 hours after that a leak was detected and reported, a first explosion occurred.