The suspected cause was a mixture of oxygen and hydrogen that passed downstream from the electrolysis unit into several storage vessels. Hydrogen-oxygen mixtures are very hazardous. Subsequent…
There is some indication that toroidal rings can reduce static buildup and ignition of hydrogen from a vent. However, while toroidal rings may help with static, they have not been proven to…
There are many designs of storage systems where multiple vessels might be needed to obtain the required storage quantity. Regulations differ between vessels and modules which are intended for…
Yes, and this is frequently done. A redundant vent stack might have its own independent redundant relief devices, or it may take the form of a secondary stack attached to the same devices. When a…
Rupture panels can add an additional layer of overpressure protection against internal overpressure. Given the propensity of hydrogen to generate higher over-pressures when ignited compared to…
While not required, Safety Instrumented Systems with a specific SIL rating are often used on hydrogen systems. The hazard analysis provides guidance as to whether a SIL rating for a given exposure…
There are no differences in the process design of the vent stack since the venting requirements will follow the same sizing and pressure rating requirements regardless of vent configuration.…
It depends on the facility and risk assessment, but generally multiple pressure and temperatures to one vent stack is not the best practice unless all are similar in pressure and temperature, and…
A vent system should still be installed in case the flare system does not remain ignited.
The regulations for electrical classification in Europe and a US jurisdiction such as California are significantly different and should not be assumed to be the same. Consultation with Authorities…
Each system must be evaluated individually, and it depends on the amount and location of possible
releases. Routing vent lines to a vent stack is the most common approach when venting directly…