Skip to main content

Category

Detectors, Pressure Relief Devices

Category

Detectors, Pressure Relief Devices

Safety codes globally have a requirement to provide a positive means to isolate energy sources and hazardous substances prior to performing maintenance. For gaseous hydrogen systems, methods such as a blind flange, a double block valve arrangement or a double block and bleed valve arrangement can provide that positive isolation.

Installing a blind flange requires breaking the supply line…

Keywords: Valves, Codes

Pressure relief systems may use reclosing devices like relief valves, non-reclosing devices like rupture discs, or a combination of both in parallel. Some systems may also be equipped with emergency blowdown systems that are operated by control systems. Selection of the proper devices is dependent on the system design and relative hazards. Variables that affect the selection include the type…

API 520, Sizing, Selection, and Installation of Pressure-relieving Devices Part I - Sizing and Selection, was written for use in the process industries in gas and liquid service.

CGA S1.3, Pressure Relief Device Standards-Part 3-Stationary Storage Containers for Compressed Gases was written for fixed equipment in gas service.

Which standard to use depends on the choice by the owner…

Equation 6.3.1.1 in CGA S1.3 is based on modeling to API methods described in: Heitner, T. Trautmauis, and M. Morrissey, “Relieving Requirements for Gas Filled Vessels Exposed to Fire,” 1983 Proceedings-Refining Department, Volume 62, American Petroleum Institute, Washington, D.C., pp. 112-122.

This method considers the transient nature of the vessel warming in combination with the…

An annual inspection of safety devices is recommended. Testing requirements will be based on the type of device and a quantified risk analysis. Typical replacement or function testing of relief valves is between 5 and 10 years depending on the application within the industrial gas industry. Rupture discs are not tested but are frequently replaced on an interval based on manufacturer…

It depends on the service. Variables include disk design, corrosion resistance, number of cycles, and how to close the operating pressure is to the rupture disc set pressure. One approach is to ask the manufacturer for their recommendation. Typical practice for U.S. Department of Transportation vessels and discs is to replace them at the tube requalification (i.e., every 5 to 10 years in the U…

The answer could be no devices at all, just a TPRD, just a PRD, or both. It depends on the potential overpressure scenarios identified during a hazard assessment. TPRDs typically are not used on ASME pressure vessels since they are not ASME compliant devices and since  system siting provides protection from engulfing fires. However, TPRDs are frequently used in portable applications for…

The Panel is not aware of any standard for hydrogen detectors for onboard vehicle applications. Some information is available in the SAE Technical Information Report: TIR J3089 Characterization of On-Board Vehicular Hydrogen Sensors, which was published in 2018.

Category: Detectors

One pertinent reference is a Sandia National Laboratories paper by Schefer et al: Spatial and radiative properties of an open-flame hydrogen plume, Intl J. Hydrogen Energy, 31 (2006): 1332-1340. Information on this and other similar papers are available at https://h2tools.org/bibliography. Further information can probably be obtained from the author of this paper and other papers reporting…