Skip to main content
Category: Lab Equipment
Keywords: Laboratory, Materials, Piping, Tubing, Outdoors, Storage, Separation Distance, Indoors, Fire Protection, System Design, Ignition Energy, Ignite, Fire, Explosion, Purge, Nitrogen, Helium, Forming Gas, Environment, Vent, Fume Hood, Vent Stack, Tools, Non-Sparking, Flammable, Hazards Analysis, Consequences, Risk, Emergency Response, Joint, Compression Fitting, Cylinder, Storage

Such a compressor should NOT be used for hydrogen. There are many issues with converting a compressor to hydrogen service. First and most important, this must be approved by the manufacturer. Examples of concerns for a non-hydrogen compressor used for hydrogen service include (but are not limited to): 

  1. Are the materials compatible with hydrogen permeation, embrittlement,…
Category: Lab Equipment
Keywords: Compressors, Hydrogen, Nitrogen, Compatibility

Even if a small experiment is being run inside a fume hood, the best practice is to use a dedicated vent line for hydrogen which vents hydrogen to a safe location outside.  This is especially recommended for planned venting.   This practice avoids situations where flammable mixtures could develop. Each system is unique and should be evaluated and approved for  use independently…

Category: Lab Equipment
Keywords: Laboratory, Venting

NFPA 2 provides Tables in Chapters 7 and 8 that specify the hazardous area classifications surrounding vent stack outlets. These are based on typical vent systems and flows, but are only applicable for smaller systems. The designer of a vent system should apply the principles of documents such as IEC 60079-10-1 (also required by NFPA 2) or NFPA 497 to evaluate larger vent releases where the…

Category: Site Planning
Keywords: NFPA 2, Hazards, Classification

Guidance for location of vent stacks is provided by NFPA 2, Hydrogen Technologies Code, which also references CGA G5.5, Hydrogen Vent Systems, for additional guidance. Minimum distances to vent stack outlets should be determined from dispersion and radiation analyses. The height of the vent stack and orientation of the release will affect the minimum separation distance.

Category: Site Planning
Keywords: Vent Stack, Separation Distance, Dispersion, NFPA 2

Dispersion and radiation analysis should be conducted to ensure that the hydrogen cloud will not interfere with the flight path of aircraft. In addition, there may be maximum height requirements due to airport requirements depending on the location of the stack.

Category: Site Planning
Keywords: Vent Stack, Airfield, Dispersion Analysis

Documents such as NFPA 2, Hydrogen Technologies Code, and the International Fire Code have quantity thresholds that differentiate requirements for the design of systems and enclosures. However, even the smaller quantities present a hazard under specific conditions, especially for systems that have the potential to release hydrogen into a confined or unvented space. Good engineering judgement…

Category: Site Planning
Keywords: Safeguards, NFPA 2, Indoors

Cylinders used within a laboratory can be used safely by meeting the requirements prescribed in NFPA 2,
Hydrogen Technologies Code, and NFPA 45, Standard on Fire Protection for Laboratories Using Chemicals.
Special consideration should be given to both safe handling and storage of cylinders. Regarding lecture
size cylinders, their small size can make them susceptible to damage and…

Category: Lab Equipment
Keywords: Cylinder, NFPA 2, NFPA 45

Each installation should be evaluated based on the results of a hazard analysis considering both of these
scenarios. Separation distances as listed in documents such as NFPA 2, Hydrogen Technologies Code, are
a minimum starting point but may need to be adjusted based on analysis. Recent work by NFPA 2 has
also included overpressure criteria, but the consequences can vary depending on…

Category: Site Planning
Keywords: Separation Distance, Overpressure, Jet Fire, NFPA 2

Each system should be evaluated for exposure of equipment to jet fires. The design team should develop
a plan to mitigate exposure as part of the hazard analysis. Fire barriers, walls, enclosures, and insulation
systems are frequently installed to meet code requirements where separation distances are not
sufficient or where the probability of exposure to a jet fire is high. Barriers…

Category: Site Planning
Keywords: Fire Protection, Jet Fire, Fire Barriers, Hazards Analysis
We are professional and reliable provider since we offer customers the most powerful and beautiful themes. Besides, we always catch the latest technology and adapt to follow world’s new trends to deliver the best themes to the market.

Contact info

We are the leaders in the building industries and factories. We're word wide. We never give up on the challenges.

Recent Posts