Should overpressure due to delayed ignition of a hydrogen release as well as jet fires be considered when setting separation distances?

Each installation should be evaluated based on the results of a hazard analysis considering both of these
scenarios. Separation distances as listed in documents such as NFPA 2, Hydrogen Technologies Code, are
a minimum starting point but may need to be adjusted based on analysis. Recent work by NFPA 2 has
also included overpressure criteria, but the consequences can vary depending on system design and
surroundings.

Category
Site Planning
Keywords
Separation Distance
Overpressure
Jet Fire
NFPA 2
Submission Year
2023
Month
04