Mesh at vent outlet can result in a fire at the vent. Is there any code suggesting that for hydrogen vent mesh?
Vent stacks must be designed for a fire at the outlet. The mesh is designed to ensure no blockage of the vent stack by animals/insects.
Additionally, the mesh must be designed for pressure drop to ensure code-compliant back pressure on the relief devices.