Mesh at vent outlet can result in a fire at the vent. Is there any code suggesting that for hydrogen vent mesh?

Vent stacks must be designed for a fire at the outlet. The mesh is designed to ensure no blockage of the vent stack by animals/insects. 

Additionally, the mesh must be designed for pressure drop to ensure code-compliant back pressure on the relief devices.

Category
System Design
Keywords
Vent Stack
Mesh
Pressure
Pressure Relief Device
Submission Year
2024
Month
01