An explosion occurred in a electrolyzer cell, the vent blew up and caused a pipe rupture on the low pressure chlorine pipeline. The event occurred when two operators were improving the tightness of…
During chlorine-alkali electrolysis an accident occurred in which chlorine was released due to a chlorine-hydrogen explosion. The person charged with the control of the measurements was informed by…
In a chlorine electrolysis facility, a mixture of oxygen and hydrogen in one of the electrolyzer cells a short-circuit ignited causing a deflagration. The cover of the cell was a thin plastic film…
The event occurred at the chlorine drying towers. The towers, made of PVC, exploded suddenly and violently in a mercury amalgam cell chlorine plant. Because of failure of the electrical power system…
An explosion occurred at a chlorine production plant during the restart of the installation. An hydraulic syphon had probably been blocked by fire extinguishing products following a previous fire on…
A lightning strike caused a voltage drop on the power supply of a chlorine-alkali plant using the mercury process.The emergency electrical system was activated, though restoring the external supply…
Explosion in an electrolyzer producing chlorine The explosion occurred after the opening of an auxiliary circuit-breaker. The opening of the auxiliary circuit breaker trigger the shut down of the…
In a chlorine manufacturing unit, an explosion occurs in the room of the electrolysis cells. The accident occurs during the start-up phase of the unit, it is due to the presence of hydrogen in the…
"A chlorine suction pump failed on a sodium hydroxide electrolysis unit.Recovery operations were carried out including nitrogen purging of hydrogen piping and air purging of chlorine piping before…
The pressure vessel in a chlorine separation system exploded after the corrosion of the steel process equipment allowed chlorine and hydrogen to mix and form a volatile mixture. The chlorine…
The incident occurred at a tank of the chlorine electrolyzer of a water treatment plantThe plant products were sodium hypochlorite as a disinfectant for water treatments. The production process used…
Fire in chemical plant (Seveso-classified)The fire developed at the top of the flare stack of a during a violent thunderstorm.The flare stack is used to discharge hydrogen produced by the…
Two successive fires broke out in an interval of few minutes in four cells in the electrolysis room of a chlorine production plant. The technicians brought the fire under control using the fire-…
Chlorine was released in the liquefaction unit of a chlorine electrolysis plant, due to the rupture of a pipe. During the re-start phase of an electrolysis workshop in a chemical plant, chlorine (…
The fire started in a electrolysis cell. The fire originated from a hydrogen leak in the hydrogen over pressure control system of the cell and an unidentified ignition source. The ARIA report (sew…
First an explosion and then a fire occurred on the condensate piping of an chlorine electrolysis plant (SEVESO upper tiers). Flames escape from the end of the pipe and spill into a 75 m open sky tank…
In an chlorine production plant, vented chlorine and hydrogen, auto ignited when the hydrogen concentration was allowed to exceed 5% and the mixture mixed with air.
An explosion occurred in the hydrogen washing tower of a chlorate plant caused by the breaking of the rupture diaphragms on the tower cover. The discharged hydrogen ignited, causing a minor leakage…
Hydrogen explosion at a chlorine chemical production plant (Seveso-classified) The plant had been shut down for two weeks, and maintenance works were ongoing. Two subcontractor employees were…
Failure of a strainer allowed sand from brine filters to get into mercury cells in a chlorine plant. It appears that the sand obstructed flow and caused excessive hydrogen generation. An explosion…