Skip to main content

Category

Hazards Analysis, Properties

Category

Hazards Analysis, Properties

A design condition for vent stacks is to always assume that the hydrogen will ignite. The stack musts be designed such that it can withstand those conditions as well as minimize radiation to surrounding personnel and exposures. Although hydrogen fires have comparatively low radiation compared to hydrocarbon fuels, the radiation from large releases from vent stacks can be quite high. Documents…

Category: Properties
Keywords: Fire, Radiant, Heat of Combustion, Vent Stack

The purity required will be a function of the end use application. There are a variety of grades of hydrogen that can be purchased. The H2 purity will also vary based on source (GH2 or LH2) and production method. CGA G-5.3, Commodity Specification for Hydrogen, lists several typical purities of both liquid and gaseous hydrogen. Standard GH2 available from most suppliers is 99.95% hydrogen.…

Category: Properties
Keywords: Purity, Requirements, Specifications

Yes, although not as common as high-pressure gas releases, high-velocity cold H2 gas has ignited during rupture disc and relief valve activation.

Category: Properties
Keywords: Rupture Disc, Ignition

The water vapor cloud formed from venting cold hydrogen gas from a liquid hydrogen tank will vary in size depending upon atmospheric conditions including ambient temperature and humidity. There is not a direct relationship between the water vapor cloud and the flammable cloud of hydrogen, but it’s often used as a proxy. 


Initially upon release, it is possible that H2 vapor from…

Category: Properties
Keywords: Plume, Dispersion, Vaporization
Category:
Keywords:

The “Hydrogen Ready Appliances Assessment Report” published by the Northwest Energy Efficiency Alliance (NEEA) in February, 2023, is one of the most recent studies on this topic.  Several key items from the report pertaining to this question include the following:

1.    “There appears to be growing consensus that blends of up to 20% or perhaps even 30% are…

Category: Properties
Keywords: Hydrogen, Blending, Appliances, Residential, Flame, Odor

CGA G-5.5 states: All vent stacks shall be grounded and meet the requirements of NFPA 70, National Electrical Code, for integrity and system design and also references NFPA 77, Recommended Practice on Static Electricity, and NFPA 780, Standard for the Installation of Lightning Protection Systems. 

For lightening refer to NFPA 780 and for grounding of the Hydrogen equipment, refer to…

Category: Hazards Analysis
Keywords: Vent Stack, Requirements, Grounding, NFPA

AICHE ELA253 CHS ” Introduction to Hydrogen Safety for First Responders” is a good reference and discusses both LH2 and GH2. LH2 fires are very unusual. LH2 releases usually are GH2 so the fires at either ambient for low flow or the GH2 is a cryo temperature for high flow. Fires from LH2 tanks ignite less frequently than GH2 high-velocity releases. The colder the gas the less potential for…

Category: Hazards Analysis
Keywords: First Responders, Safety, LH2, GH2, Guidelines, Fire Protection