All vent stacks/systems should be bonded and grounded to minimize ignition sources. Higher pressure streams from higher velocities have a greater risk of igniting for several reasons, including particle impingement. Adding mesh could create more impact points for particulate, which would increase the potential for ignition, but would not increase the probability of a DDT. Similarly, high flow…
There is no standard which specifically specifies the use of a flapper. A properly designed flapper should provide de minimus restriction to vent flow, yet still provides weather protection which allows for a vertical release of the vent stack flow, which is best from a dispersion and radiation perspective. Flappers are extensively used successfully and safely on nearly all liquid hydrogen…
I am not sure which picture you are referring to so I will attempt to answer.
If you are referring to the incident where a fire occurred and the vent system was damaged, then this may have been due to lack of proper supports and incomplete assembly of the test systems. In the past, vent systems were not pressure tested for strength but that is changing.
If you are talking…
At NASA Cape Canaveral, they used a natural gas line connected to the vent stack outlet with a thermal sensor to make sure the pilot was lit. They may also have had a sensor to ensure the H2 fire was lit. In cases where substantial quantities of unused hydrogen is vented and the timing and amount of the flow rate is known and controlled, flaring might be useful. NASA guidelines stipulate that…
There is no specific requirement not to vent liquid hydrogen from a vent system. Best practice would be to only vent gas from the top of the vessel to relieve pressure. If liquid must be vented, it should be vaporized first.
Note: It is very unusual to have LH2 flow from a liquid tank out the vent system, as the vent system is connected to the vapor space on the LH2 tanks and there…
No, but it depends on the application. Nearly all vents less than 4” in size are not purged with N2. This is primarily due to: 1) large flows required to dilute hydrogen below the flammable range, 2) the cost of the nitrogen, 3) the potential blockage of the stack when being inserted a vent header/stack serving a liquid hydrogen system, 4) the potential for backpressure (depending on the…
Example safety guidelines are listed below but may not be all-inclusive (e.g., they do not cover general practices such as lockout/tagout, management of change, job safety analysis), and most are the same as for gaseous hydrogen. Also reference NFPA 2 and CGA documents such as H-3, H-5, and H-7. Additional safety training material can also be found on the following link to courses and…