- Home
-
Resources
- Center for Hydrogen Safety
- Hydrogen Fuel Cell Codes and Standards
- Learnings & Guidance
- Paper & References
- Web-based Toolkits
- Contact
- About H2Tools
It is normal for some air ingress to occur from the vent stack outlet. This is not a hazard if the stack has been properly designed to withstand an internal explosion or fire. Once hydrogen flow from a device is initiated, it will sweep out any air that might be in the stack. Generally, if the vent rate is insufficient to sweep the air out, then it’s also insufficient to freeze or liquefy air…
The colors of hydrogen are not different hydrogen molecules. The colors represent the different methods to produce hydrogen. The colors are based on how much carbon is produced into the atmosphere during the manufacture of hydrogen.
That being said there is no difference in hydrogen vent systems design by color, only by the design parameters (i.e. temperature, pressure, flow rate,…
Recommended limits of heat flux for various exposures is provided in documents such as API Standard 521, the International Fire Code, the National Fire Protection Association and the Society of Fire Protection Engineers. Selection of a specific thermal radiation level is dependent upon a risk analysis. Some salient exposures are listed below.
We would not open the vent system to inspect the internal piping without a good reason.
It is recommended to check for water in the vent stack trap
Purging is not recommended as a continuous part of vent stack operation. However, maintenance activity is a transient event and it’s prudent and recommended to purge a vent system prior to performing maintenance. It’s always possible that hydrogen could be leaking internally from a valve or other component and therefore create a hazard. Of particular note, care must be taken that proper…
In general, indoor storage should be limited and the use of hydrogen indoors should be the least necessary. Look to store flammable gases outdoors in dedicated protected area when practicable. Check to see what adopted building and fire codes in your jurisdiction say. NFPA 2, Hydrogen Technology Code, Sections 6.4.1 and 16.3 prescribe requirements to limit hydrogen storage and use in…
Because hydrogen leaks frequently ignite, and because about half the time the ignition source is not identified, when evaluating hazards with hydrogen leaks, many people just assume the leak will be ignited. Note that consideration needs to be made for what may happen with immediate ignition (jet fire) and what may happen with delayed ignition (explosion).
It is still important to…
Flare-less compression style fittings are commonly used. Choose tubing materials and tube wall thicknesses suitable for hydrogen and pressures you are using. Make sure all tubing joints are properly made, mechanically supported to minimize stress and vibration, are in a ventilated space, and are easily accessible for inspection and leak testing.
Liquid hydrogen is rarely vented as a liquid. If liquid hydrogen is vented, there should be a means to ensure that it is fully vaporized. The vent systems for LH2 tanks are connected to the vapor space on the tanks to ensure in most instances, this occurs. Most vents from a liquid hydrogen system will vent gaseous hydrogen, but this gas, may still be as cold as -420 F. There are no code…
We are the leaders in the building industries and factories. We're word wide. We never give up on the challenges.