- Home
-
Resources
- Center for Hydrogen Safety
- Hydrogen Fuel Cell Codes and Standards
- Learnings & Guidance
- Paper & References
- Web-based Toolkits
- Contact
- About H2Tools
Several organizations published a paper together on this topic in 2017 (see attached). Based on comparisons with tests and CFD simulations, the following conclusions were drawn:
The code used for repair and alterations of an existing system depends on the code used for construction as well as on the requirements imposed by the jurisdiction. Note that getting a permit from the jurisdiction may be necessary for an extensive alteration.
Code of Construction | Generally Accepted Code for Repair and Alterations… Category: Piping Keywords: Piping, Codes
The requirements of the code used for the original construction apply. The piping may meet the requirements of more than one code. In which case, the code used for changing the rating may be different than the original code of construction. In any case, the re-rated system should meet all of the requirements of the selected code. Note that if the original proof test of the system was… Category: Piping Keywords: Codes, Piping, Requirements
At least three of the ASME B31 piping codes are logical choices:
Considerations for code selection include:
Category: Piping Keywords: Piping, Codes, Requirements
There are two parts for such a system to be effective. First, the system would have to activate quickly enough to establish a water mist throughout the region of interest (i.e., region occupied by a flammable gas mixture) before it could be ignited. This is challenging in terms of timing, and the impact of spraying water inside an enclosure filled with equipment not designed to get wet can be… Category: Explosions Keywords: Explosion, Mitigation, Prevention Water Spray
Explosion testing with hydrogen should be utilized only where there is not an established alternative and then only by personnel experienced in such testing. Category: Explosions Keywords: Explosion, Testing, Burning Velocity
The Panel has not received such inquiries. Section 14.2 of NFPA 69 Standard for Explosion Prevention Systems covers foam and mesh requirements. NFPA 69 states in 14.3.4 that the tests shall be conducted with a flammable gas/air mixture with a fundamental burning velocity representative of the burning velocities of flammable vapors expected in the intended applications. Category: Explosions Keywords: Explosion, NFPA 69, Foam, Mesh, Prevention
I am communicating with a company that is exploring this technology for an application involving a mixture of flammable gases, including hydrogen. Category: Explosions Keywords: Explosion, Prevention, Foam, Mesh
No, but it is always necessary to determine the possibility of an adverse chemical reaction with the particular material being used for the mesh. Category: Explosions Keywords: Explosion, Prevention, Foam, Mesh
There is limited published research on the effect of water sprays on hydrogen deflagrations and deflagration-to-detonation transition, and more extensive data on water spray effects on hydrocarbon gas explosions. The results show the benefits, where there are benefits, to be highly scenario dependent. For example, Carlson et al. (Atomics International report, 1973) described hydrogen… Category: Explosions Keywords: Explosion, Mitigation, Prevention Water Spray
We are professional and reliable provider since we offer customers the most powerful and beautiful themes. Besides, we always catch the latest technology and adapt to follow world’s new trends to deliver the best themes to the market.