Skip to main content

1.    As of January 2024, we are not aware of any public data on incidents or investigations where a hydrogen fired steam boiler exploded.

2.    The potential for detonations within a boiler tube would depend on both the equivalence ratio of the hydrogen present and the diameter of the boiler tube.
a.    At a minimum, if the circumference of the tube is…

Category: Explosions
Keywords: Detonation, Deflagration, Equipment, Explosion, DDT

The Panel recommends performing a pressure test at 110% of design pressure. This requirement should be applied to all systems regardless of construction type since the intent is to ensure pressure integrity and proper installation. All fitting types have modes of failure during installation. For example, there are numerous examples where compression fittings have had ferrules installed…

Category: Piping
Keywords: Piping, Leak, Testing, Pneumatic

The HSP recommends against the use of glycols for pressure tests due to the difficulty of adequately removing all glycol that might be left in a system after a hydrotest. The HSP recommends a pneumatic test at 110% of the system maximum allowable working pressure (MAWP), which is acceptable by code. Due to an increased danger with pneumatics vs hydrotesting, establish a pressure test zone for…

Category: Piping
Keywords: Piping, Leak, Testing, Glycol, Freezing, Pressure

Yes, these would be ignitable mixtures.  In this case, it does not appear complicated geometry is involved, so 1200 psig pipe should be more than adequate to protect against internal deflagration. The most likely scenario is a "backfire," similar to a car, where ignition occurs too soon and shoots out the open end of the pipe. Consider using an inline deflagration flash arrestor on the…

Category: Explosions
Keywords: Explosion, Detonation, Piping, System Design

NFPA 2 provides Tables in Chapters 7 and 8 that specify the hazardous area classifications surrounding vent stack outlets. These are based on typical vent systems and flows, but are only applicable for smaller systems. The designer of a vent system should apply the principles of documents such as IEC 60079-10-1 (also required by NFPA 2) or NFPA 497 to evaluate larger vent releases where the…

Category: Site Planning
Keywords: NFPA 2, Hazards, Classification

Guidance for location of vent stacks is provided by NFPA 2, Hydrogen Technologies Code, which also references CGA G5.5, Hydrogen Vent Systems, for additional guidance. Minimum distances to vent stack outlets should be determined from dispersion and radiation analyses. The height of the vent stack and orientation of the release will affect the minimum separation distance.

Category: Site Planning
Keywords: Vent Stack, Separation Distance, Dispersion, NFPA 2

Dispersion and radiation analysis should be conducted to ensure that the hydrogen cloud will not interfere with the flight path of aircraft. In addition, there may be maximum height requirements due to airport requirements depending on the location of the stack.

Category: Site Planning
Keywords: Vent Stack, Airfield, Dispersion Analysis

Hydrogen affects the mechanical properties of most materials. For example, hydrogen reduces the
fracture toughness and increases the fatigue crack growth rate in steels. There is a significant amount of
research, analytical work, and codes and standards development being undertaken to improve our
understanding of how these materials can be utilized in pipelines. The results of the…

Category: Piping
Keywords: Pipeline, Material Compatibility, ASME Standards, Pipeline Safety

Because cast irons are relatively brittle materials, they should generally be avoided in industrial and
transmission pipeline applications. In low pressure applications like residential distribution piping
systems, the use of cast irons is probably acceptable.

Category: Piping
Keywords: Cast Iron, Pipeline, Low-pressure systems, ASME Standards

Acceptability of materials is highly dependent on the specific application. Applied stress levels, exposure to contaminants, the operating temperature, the partial pressure, and number and magnitude of material stress cycles are some of the factors that affect material selection. Guidance is provided within documents such as ISO 11114, Gas cylinders - Compatibility of cylinder and valve…

Category: Piping
Keywords: Material Compatibility, Piping, Austenitic Stainless Steel, ASME Standards