- Home
-
Resources
- Center for Hydrogen Safety
- Hydrogen Fuel Cell Codes and Standards
- Learnings & Guidance
- Paper & References
- Web-based Toolkits
- Contact
- About H2Tools
1. As of January 2024, we are not aware of any public data on incidents or investigations where a hydrogen fired steam boiler exploded.
2. The potential for detonations within a boiler tube would depend on both the equivalence ratio of the hydrogen present and the diameter of the boiler tube.
a. At a minimum, if the circumference of the tube is…
The Panel recommends performing a pressure test at 110% of design pressure. This requirement should be applied to all systems regardless of construction type since the intent is to ensure pressure integrity and proper installation. All fitting types have modes of failure during installation. For example, there are numerous examples where compression fittings have had ferrules installed…
The HSP recommends against the use of glycols for pressure tests due to the difficulty of adequately removing all glycol that might be left in a system after a hydrotest. The HSP recommends a pneumatic test at 110% of the system maximum allowable working pressure (MAWP), which is acceptable by code. Due to an increased danger with pneumatics vs hydrotesting, establish a pressure test zone for…
Yes, these would be ignitable mixtures. In this case, it does not appear complicated geometry is involved, so 1200 psig pipe should be more than adequate to protect against internal deflagration. The most likely scenario is a "backfire," similar to a car, where ignition occurs too soon and shoots out the open end of the pipe. Consider using an inline deflagration flash arrestor on the…
Hydrogen affects the mechanical properties of most materials. For example, hydrogen reduces the
fracture toughness and increases the fatigue crack growth rate in steels. There is a significant amount of
research, analytical work, and codes and standards development being undertaken to improve our
understanding of how these materials can be utilized in pipelines. The results of the…
Because cast irons are relatively brittle materials, they should generally be avoided in industrial and
transmission pipeline applications. In low pressure applications like residential distribution piping
systems, the use of cast irons is probably acceptable.
Acceptability of materials is highly dependent on the specific application. Applied stress levels, exposure to contaminants, the operating temperature, the partial pressure, and number and magnitude of material stress cycles are some of the factors that affect material selection. Guidance is provided within documents such as ISO 11114, Gas cylinders - Compatibility of cylinder and valve…
Hydrogen has been transported safely through pipelines for over 50 years. There are dozens of pipeline networks in safe operation globally, with several individual networks that approach up to 1000 miles.
Significant testing and some demonstration projects are underway to ensure safety. Some of the aspects under investigation include compatibility of the pipe and other materials,…
The conversion is based on the condition as determined from a variety of non-destructive techniques which are commonly used for pipeline mechanical integrity programs. Existing natural gas pipelines are frequently evaluated for conversion to hydrogen, hydrogen-natural gas blend, and other fluid services.
The conversion can be done safely if handled with the proper expertise and…
Double pipes can be used in certain circumstances to reduce the likelihood of external leaks and increase
the likelihood of detection by monitoring the space between the two pipes. Vacuum jacketed piping is
double walled and is used in liquid hydrogen service to provide insulation. While not equipped with gas
detection in the annular space, loss of vacuum is used to indicate an…
We are the leaders in the building industries and factories. We're word wide. We never give up on the challenges.