Passive fire protection barriers are often used to protect structures and equipment from hydrogen jet fires, especially in high-risk or code-driven scenarios.

Are passive fire protection barriers typically provided to protect structures, pipe racks, etc., against hydrogen jet fires?

Each system should be evaluated for exposure of equipment to jet fires. The design team should develop
a plan to mitigate exposure as part of the hazard analysis. Fire barriers, walls, enclosures, and insulation
systems are frequently installed to meet code requirements where separation distances are not
sufficient or where the probability of exposure to a jet fire is high. Barriers are sometimes installed for
high risk exposures such as storage vessels, even if not required by Code rules.

FAQ Category
Submission Year
2023
Month
04

Separation distances should account for overpressure from delayed ignition and jet fires, with adjustments guided by hazard analysis and standards like NFPA 2.

Should overpressure due to delayed ignition of a hydrogen release as well as jet fires be considered when setting separation distances?

Each installation should be evaluated based on the results of a hazard analysis considering both of these
scenarios. Separation distances as listed in documents such as NFPA 2, Hydrogen Technologies Code, are
a minimum starting point but may need to be adjusted based on analysis. Recent work by NFPA 2 has
also included overpressure criteria, but the consequences can vary depending on system design and
surroundings.

FAQ Category
Submission Year
2023
Month
04

Hydrogen Jet Impingement

What information or resources are available regarding ignited H2 jets impinging on H2 tanks and the resulting failure rates, failure mode and potential impacts? Of high concern to the project in question are sustained, ignited H2 jets from non-isolatable fittings impinging on steel H2 storage. The severity of a sustained H2 jet on a type 4 tanks (with only a PSV) appears to be very high. Given the failure/leak rates from HyRAM combined with the station layouts, the findings thus far indicate that the risk with H2 jets impinging on type 4 tanks can be above ALARP, requiring engineering safeguards. How much more resistance would steel tanks have compared to type 4 tanks?

Type 1 steel tanks can be cut with a welding torch, so they can definitely be impacted by flame impingement. Above 400-500 C° the material properties of steel will start to degrade.

It is challenging to protect a vessel, either Type 1 steel or composite Type 2, 3, or 4 from an impinging fire since the safety devices may not see the elevated temperatures in the area of impingement. Devices such as thermally activated pressure relief devices (TPRDs) or rupture discs are usually the best for fire exposure since when activated, they fully depressurize the contents to relieve stresses on the vessel walls. However, TPRD’s will not activate properly to relieve the contents unless exposed to the heat of the localized impinging fire. Similarly, a rupture disc may not activate unless the pressure increases to its setpoint or unless it’s weakened by the impinging fire. Relief valves may activate if the pressure rises but will maintain pressure until the walls potentially weaken below the stress imparted by the pressure even if at or below the MAWP.

Composite tanks are even more susceptible to impingement fire since the materials are not as robust as steel. In particular, the resin used for the composite material may weaken at temperatures as low as 100 C°. The resin and fiber materials also may be flammable and result in further weakening as the fire continues. Composite vessels are usually protected with TPRDs but have the limitation mentioned above. Generally, Type 1 steel vessels are likely to withstand a hydrogen jet flame longer than a composite vessel because of the difference in materials and the lower mass and thickness.

 
Impingement may best be addressed by ensuring that the hardware design of the project largely eliminates likely sources of a non-isolatable leak/jet fire.  A good system design would not have any hardware beyond the cylinder shut-off valve itself that could create this scenario by utilizing good pipe routing/geometry.  A solution could be a fire barrier either directly applied to the vessel (such as a coating system) or as a stand-off shield or wall to block the fire impingement.  In addition, for some projects fire suppression systems such as sprinklers may be appropriate.  They won’t put out the jet fire, but they can help keep other surfaces cool. A thorough hazard analysis should be part of any project design.  
 