Skip to main content

For a flare stack a radiation study is normally required. Is a radiation study necessary for vent stacks as well?

Yes, for all stacks. GH2 has a minimum prescriptive height of 10 ft. There is no minimum prescriptive height for LH2. However, 25 ft has been a best practice for the industry for years. Vent stack outlets that orient the release vertically help reduce the radiation exposure at ground level. Care must be taken to consider varying weather conditions, particularly wind, as well as surrounding exposures that might be elevated in the vicinity of the vent stack outlet, such as nearby equipment, buildings, catwalks, and grade elevation changes. 

Category
System Design
Keywords
LH2
GH2
Flare
Vent Stack
Submission Year
2024
Month
01
We are professional and reliable provider since we offer customers the most powerful and beautiful themes. Besides, we always catch the latest technology and adapt to follow world’s new trends to deliver the best themes to the market.

Contact info

We are the leaders in the building industries and factories. We're word wide. We never give up on the challenges.

Recent Posts