Hydrogen fuel cells have been installed in more than 100 facilities and numerous homes in Ulsan hydrogen town in the Republic of Korea. Despite the advantages of hydrogen, accidents can still occur near residential areas. Thus, appropriate risk mitigation plans should be established. In this study, a computational fluid dynamics (CFD) model of natural and forced ventilation is presented as an emergency response to hydrogen leakages in pressure regulator equipment housing. The CFD model is developed and investigated using three vent configurations: UP, CROSS, and UP-DOWN. The simulation results indicate that the UP-DOWN configuration achieves the lowest internal hydrogen concentration out of the three. In addition, the relationship between the total vent size and internal hydrogen concentration is determined. A vent size of 12% of the floor area has the lowest hydrogen concentration. The use of nitrogen for forced ventilation during emergencies is proposed to ensure that the hydrogen concentration of the released gas is less than one-fourth of the lower flammability limit of hydrogen. Compared to natural ventilation, the time required to reach safe conditions is decreased when nitrogen forced ventilation is used.(c) 2022 The Author(s). Published by Elsevier Ltd on behalf of Institution of Chemical Engineers. CC_BY_4.0

Year of Publication
2022
Journal
Process Safety and Environmental Protection
Volume
161
Number of Pages
436-446
Type of Article
Article
ISBN Number
0957-5820
Accession Number
WOS:000806147100002
DOI
10.1016/j.psep.2022.03.065
Alternate Journal
Process Saf Environ
We are professional and reliable provider since we offer customers the most powerful and beautiful themes. Besides, we always catch the latest technology and adapt to follow world’s new trends to deliver the best themes to the market.

Contact info

We are the leaders in the building industries and factories. We're word wide. We never give up on the challenges.

Recent Posts