We present results from hydrogen dispersion simulations from a pressurized reservoir at constant flowrate, in the presence and absence of a wall. The dispersion simulations are performed using acommercial finite volume solver. Validation of the approach is discussed. Constant concentrationenvelopes corresponding to the 2%2 4%2and 15%2hydrogen concentration in air are calculated for asubcritical vertical jet and for an equivalent subcritical horizontal jet from a high pressure reservoir.The consequences of ignition and the resulting overpressure are calculated for subcritical horizontaland vertical hydrogen jets and in the latter case, compared to available experimental data.