A facility is described that allows safe handling of high tritium gas activity as dozens kilocuries in a regular laboratory environment. It is used to make and deliver into the target a mixture of specific isotopic composition with the contamination requirement of 10(-7) v.f. for Z>1 elements, and recover it upon completion of operation. With this facility, efforts have been accomplished to investigate into the muon catalyzed fusion on two targets - liquid tritium and high-pressure tritium types. Also, the operation range was 0.1-120 MPa for pressure and 20-800 K for temperature and the amount of tritium used was about 100 kCi. The facility showed reliability in operation without indications of radiation beyond the safety level.