Flame arrestors are rarely needed in hydrogen systems but may be considered if risks justify their use and flow restrictions are addressed.

Is installing a flame arrestor at the vent generally accepted practice?

The suitability of flame arrestors depends on the design of the system, but generally flame arrestors are
rarely needed for hydrogen systems when there is a 100% hydrogen atmosphere upstream of the vent,
and when the downstream vent system is designed to withstand internal ignition. Flame arrestors can
also cause potential blockage or restriction of flow, so relative risks need to be carefully assessed when
they are installed on vent lines.

FAQ Category
Submission Year
2023
Month
04

Are flame arrestors for GH2 stacks recommended

What about the use of flame arrestors for GH2 stacks? Are they recommended? If not, why not?

Flame arrestors can be installed on hydrogen gas vents. The purpose of a flame arrestor is to prevent the migration of flame backwards and upstream into the vent stack or system itself. Generally, flame arrestors are not needed since: 1) the vent stack should be designed to withstand fire or explosion within the stack, and 2) the process generally does not contain a flammable mixture within it, so there is no danger of the flame propagating into the system. In these cases, flame arrestors are not needed and should be avoided since they create additional hazards of blocking or restricting the vent flow. 

There are situations where flame arrestors can be appropriate. An example would be a vent stack from a compressor crankcase. Compressor crankcases are often vented to atmosphere, and where there is a possibility of hydrogen leakage into the crankcase, that vent might use a vent stack to ensure that leakage goes to a safe location. Since the crankcase might then have an air-hydrogen mix, a flame arrestor can prevent the propagation of flame backwards into the crankcase if it were to ignite on the vent stack. The crankcase is usually confined and congested so it could result in an overpressure significant enough for it to rupture. 

The European Industrial Gas Association (EIGA) Doc 211/17, 7.4 does not allow flame arrestors due to the backpressure associated with them.

FAQ Category
Submission Year
2024
Month
01

Flame arrestors can be installed on hydrogen gas vents

Is it possible to install flame arrestors on hydrogen gas vent stacks?

Flame arrestors can be installed on hydrogen gas vents. The purpose of a flame arrestor is to prevent the migration of flame backwards and upstream into the vent stack or system itself. Generally, flame arrestors are not needed since: 1) the vent stack should be designed to withstand fire or explosion within the stack, and 2) the process generally does not contain a flammable mixture within it, so there is no danger of the flame propagating into the system. In these cases, flame arrestors are not needed and should be avoided since they create additional hazards of blocking or restricting the vent flow. For example, a flame arrestor on a vent stack serving a liquid hydrogen system might get cold and build up ice, thereby restricting flow.
There are situations where flame arrestors can be appropriate. An example would be a vent stack from a compressor crankcase. Compressor crankcases are often vented to atmosphere, and where there is a possibility of hydrogen leakage into the crankcase, that vent might use a vent stack to ensure that leakage goes to a safe location. Since the crankcase might then have an air-hydrogen mix, a flame arrestor can prevent the propagation of flame backwards into the crankcase if it were to ignite on the vent stack. The crankcase is usually confined and congested so it could result in an overpressure significant enough for it to rupture. The European Industrial Gas Association (EIGA) Doc 211/17, 7.4 does not allow flame arrestors due to the backpressure associated with them.

FAQ Category
FAQ Keyword
Submission Year
2024
Month
01
Subscribe to Flame Arrestor
We are professional and reliable provider since we offer customers the most powerful and beautiful themes. Besides, we always catch the latest technology and adapt to follow world’s new trends to deliver the best themes to the market.

Contact info

We are the leaders in the building industries and factories. We're word wide. We never give up on the challenges.

Recent Posts