Detonation in a Safety Cabinet Containing Hydrogen Cylinders (1006)

The safety cabinet with compressed hydrogen was located in a laboratory and used to supply hydrogen to an experimental facility. The safety cabinet was equipped with exhaust extraction. Due to a leak, technical assistance had been requested from the fire department. The head of laboratory shut off the electrical supply to the laboratory. Measurements showed that there was no potentially explosive atmosphere in the laboratory room.

Fire in a Chlorine Electrolysis Plant (917)

First an explosion and then a fire occurred on the condensate piping of an chlorine electrolysis plant (SEVESO upper tiers). Flames escape from the end of the pipe and spill into a 75 m open sky tank, containing the electrolysis products (water, HCL, NaOH, Na). According to the ARIA report, (see source) a maintenance operation was ongoing on the HCl furnace located nearby. Investigations conducted by the operator identified a design defect as the cause of the incident. The overflow of the guard hydrogen hydraulic system was wrongly connected to the condensate piping.