FCEV Hit on Rear Right Side by Vehicle Entering Road from STOP Sign (1088)

The FCEV was travelling at approx. 75 km/h (80 km/h speed limit) on a straight, downhill part of the road. Another vehicles was waiting at a STOP sign on the right side, did not see the incoming FCEV and drove into the road at the moment of the FEV passing. The second vehicle hit the FCEV on the back right side. There were only body parts damaged and no hydrogen was released. There was no oil or other fluid spillage and no people were injured.The diagnostic system of the FCEV did not issue any alarm, and there were no warning lights to indicate a problem with the hydrogen systems on-board.

Release from the Storage of a Hydrogen Production Plant (1086)

The accidental hydrogen release occurred when testing the storage system connected to a PEM electrolyzer. The leak test consisted in filling the storage with hydrogen at step-wise increase of pressure. After the step at 3 bar (0.3 MPa), which did not reveal any leak, the storage was pressurised up to 5 bar (0.5 MPa). At that moment a hissing sound occurred from the storage at the outside of the building indicating a leak.

Hydrogen/Methane Release at a Gas Booster of a Pipeline (1085)

The incident involves a gas booster provided by a manufacturer. This device is used in the experimental platform of the project to raise the pressure in pipelines from 60 to 80 barg (from 6 to 8 MPa), allowing the gas to flow in a close loop. After 5 weeks of operation, a critical gas leakage through the vent port was detected.At the moment of the incident, the compressor was working with a mixture of hydrogen and methane (H2/CH4 blend 20/80 %v/%v). The booster was sent to the manufacturer for inspection and reparation. Severe damage in the seals of the vent port was found.

Explosion at an Electrolyzer at a Refueling Station (1084)

This incident occurred at the electrolyzer of a refuelling station. An employee of the electrolyzers manufacturer was on-site to conduct a reset of the plant power breaker system and to restart gas generation. Whilst putting the system into generation, a loud bang was heard. By reviewing the station CCTV evidence, a cloud of water vapour was seen being emitted from the oxygen vent line of the electrolyzer container. The gas generation system was safely shut down, and an investigation was started to understand the cause and potential impacts.

Release from a Hydrogen Cylinders Truck (1082)

A truck-trailer carrying compressed hydrogen cylinders stopped on an autobahn and reported a hydrogen leaking from the cylinders. The highway was immediately closed in both directions. When the fire brigade arrived, the truck had stopped on a hard shoulder, and the driver had al-ready left his vehicle. A pipe was reported to be leaking hydrogen. Fire-fighters closed a valve on the affexted cylinder group to stop the leak.

Highway Truck Crash and Fire (1081)

On a highway, a truck loaded with 400 gas cylinders crashed at night for an undetermined cause against a concrete wall and overturned. It slipped 150 m, before several 200 litre cylinders of hydrogen caught fire and set the truck on fire as well. The police stated that it was a large fire with detonations. The 400 gas cylinders were connected together and many of the cylinders had fallen out of their racks. In order to reduce the danger of further explosions, the fire-brigade cooled the gas cylinders with water for two hours. The highway remained closed for eight hours.

Fire on a Hydrogen Gasholder (1078)

[NOTE: One source speak of a hydrogen gasometer, spanish news speak in general of gas, others of ntural gas or coal gas; considering the main product of the factory, it was chosen for this last version, but is is rather doubtful]This incident occurred at a coal gas storage (gasometer) system of a producer of foundry coke. The gasholder was a variable capacity tank, rising in height depending on the amount of gas stored, with a maximum capacity of 24,000 m3.Company sources said that the fire was caused as a result of a spark and a gas leak that was being repaired by the operators.

Liquid Hydrogen Tank Explosion (1076)

A 9000 gal (34 m3) LH2 storage tank exploded during repair of the vent stack. Few days before the explosion, the tank had been filled with LH2, but later on the hydrogen released and ignited at the tank pressure control system, damaging the vent stack. To perform the required repairs, the tank had to be emptied. To this purpose the vessel was purged with nitrogen gas to display the LH2 by letting it boiling. However, the pressure inside the vacuum jacket increased because of the opening the vacuum valve. This pressure increase eventually led to the catastrophic tank rupture.

Natural Hydrogen Fire (1074)

In 1987, well diggers had drilled a well for water, but had given up on one dry borehole at a depth of 108 meters. According to the source reported in the References, wind was coming out of the hole. When one driller peered into the hole while smoking a cigarette, the so-called wind exploded in his face. A huge fire followed, without smoke, looking bluish at daytime and colour and goldish at night. The crew needed weeks before being able to stop the fire and cap the well. The well remained capped until 2007, when well gas was analysed and revealed to consist in hydrogen with a purity of 98%.

Hydrogen Leak and Fire in Compressor Area of Continuous Reforming Unit (1073)

A hydrogen leakage caught fire in the hydrogen compressor area of the continuous reforming unit. The reforming unit and the hydrocracking unit were immediately stopped. The hydrogen flow was cut off, a protective combustion was carried out and the fire was completely extinguished after approximately 20 minutes, with no casualties. The cause of the accident is being investigated.