This is an impossible question to answer without greater understanding of the quantities of hydrogen involved, the types of vessels involved, and the atmospheric conditions. Several companies offer software to model such releases. It’s important to note that there is a high probability of ignition either during the vessel rupture or from nearby ignition sources.
Vaporization of a trapped volume of LH2 will lead to significant increase in pressure due to the very large expansion ratio as the liquid converts to gas. Relief devices are required since the pressure increase is likely to be far in excess of the pressure rating of the system. When vaporized as part of a flowing process, pressure will not increase. As the LH2 is warmed, it undergoes a phase…
A pressure of 600 kPa (87 psi) is relatively moderate, so the combustion properties are similar to those at atmospheric pressure where the autoignition temperature of hydrogen is 585°C.
H2-air flammability limits vary with temperature . The H2-air lower flammability limit is virtually the same as the H2-O2 lower limit. However, the H2-O2 upper flammability limit increases substantially to about 95% at room temperature and gets even higher at elevated temperatures.
…In the case of fuel-rich mixtures like those in the question, the heat of combustion for the mixture should be calculated on the basis of the oxygen content of the mixture. The heat of combustion per mole oxygen is twice the heat of combustion per mole hydrogen, i.e., it is 286*2 kJ per mole O2. You should be able to do the calculations based on this reply.
Previous versions of NFPA 55 listed overhead power lines within the separation distance tables with no voltage distinction. The separation distances were 15 ft for GH2 and 25 ft for LH2 for all overhead electrical lines. The current edition of NFPA 2 includes these in overhead utilities; the distance for GH2 and LH2 will vary with pressure and diameter of the hydrogen piping. In practice, high…
The Global Asset Protection Services (GAPS) standard was written 20 years ago for property loss prevention at crowded chemical plants and is intended for existing and new oil and chemical facilities to limit explosion over-pressure and fire exposure damage; thus, the purpose is different than NFPA 2. NFPA distances were based on studies from the 1960s as well as qualitative factors that were…
There is technically no upper limit for GH2 storage listed within the separation distance tables within Chapter 7 of NFPA 2. For LH2, there is a 75000-gallon upper limit for the LH2 storage separation distance tables within Chapter 8 for LH2.
It’s important to note that many facilities have site specific issues such as large quantities, confinement, and congestion, so it may be…
These distances are based primarily on hydrogen piping releases and resultant vapor clouds and jet flames based on pipe diameter and pressure. It’s important to note that many facilities have issues such as confinement and congestion, so it may be applicable to apply contemporary engineering models to assess risk.