The deflagration pressure is dependent upon many variables.
However, some general concepts are:
Exhaust systems (sometimes referred to as ventilation systems) are used to exhaust hydrogen and air mixtures. Normally these are used to vent streams with less than flammable range hydrogen in air.
That is, hydrogen detectors trigger venting or the ventilation systems runs during all hydrogen operations. In these instances, low concentrations of hydrogen are expected, but deflagration is…
Yes, there are differences due to the differences in the fluid properties. We’re not sure what is meant by blowdown. If this means that should the gases be vented to a vent stack, possibly, but for certain these need to be vented to a safe location.
There is currently a published ASME BPV Code Case describing pressure design requirements for pressure design of electrolyzers. If the Code Case is adopted by the jurisdiction where a new electrolyzer will be installed, the new electrolyzer will have to meet the requirements in the Code Case. The responsible ASME committee is working to revise the Code Case and intends to incorporate the Code…
Applicable EU Directives frequently include the following:
· Low Voltage - 2014/35/EU
· Machinery - 2006/42/EC
· Electromagnetic Compatibility - 2014/30/EU, EMC
· Pressure Equipment - 2014/67/EU
· Restriction of Hazardous…
When it is necessary or desirable to work on a part of a hydrogen system while another part of the system remains in operation or in standby condition. An example is a system with two compressors, where one is normally operating and the other acts as an installed spare. The two block valves are closed, and the bleed (vent) valve is open. This arrangement assures that any hydrogen leaking…
Recommended limits of heat flux for various exposures is provided in documents such as API Standard 521, the International Fire Code, the National Fire Protection Association and the Society of Fire Protection Engineers. Selection of a specific thermal radiation level is dependent upon a risk analysis. Some salient exposures are listed below.
The SRV orientation is critical for many reasons. Many of these are:
The colors of hydrogen are not different hydrogen molecules. The colors represent the different methods to produce hydrogen. The colors are based on how much carbon is produced into the atmosphere during the manufacture of hydrogen.
That being said there is no difference in hydrogen vent systems design by color, only by the design parameters (i.e. temperature, pressure, flow rate,…
It is normal for some air ingress to occur from the vent stack outlet. This is not a hazard if the stack has been properly designed to withstand an internal explosion or fire. Once hydrogen flow from a device is initiated, it will sweep out any air that might be in the stack. Generally, if the vent rate is insufficient to sweep the air out, then it’s also insufficient to freeze or liquefy air…