Skip to main content

Category

Explosions, Piping

Category

Explosions, Piping

Yes, these would be ignitable mixtures.  In this case, it does not appear complicated geometry is involved, so 1200 psig pipe should be more than adequate to protect against internal deflagration. The most likely scenario is a "backfire," similar to a car, where ignition occurs too soon and shoots out the open end of the pipe. Consider using an inline deflagration flash arrestor on the…

Category: Explosions
Keywords: Explosion, Detonation, Piping, System Design

The HSP recommends against the use of glycols for pressure tests due to the difficulty of adequately removing all glycol that might be left in a system after a hydrotest. The HSP recommends a pneumatic test at 110% of the system maximum allowable working pressure (MAWP), which is acceptable by code. Due to an increased danger with pneumatics vs hydrotesting, establish a pressure test zone for…

Category: Piping
Keywords: Piping, Leak, Testing, Glycol, Freezing, Pressure

The Panel recommends performing a pressure test at 110% of design pressure. This requirement should be applied to all systems regardless of construction type since the intent is to ensure pressure integrity and proper installation. All fitting types have modes of failure during installation. For example, there are numerous examples where compression fittings have had ferrules installed…

Category: Piping
Keywords: Piping, Leak, Testing, Pneumatic

1.    As of January 2024, we are not aware of any public data on incidents or investigations where a hydrogen fired steam boiler exploded.

2.    The potential for detonations within a boiler tube would depend on both the equivalence ratio of the hydrogen present and the diameter of the boiler tube.
a.    At a minimum, if the circumference of the tube is…

Category: Explosions
Keywords: Detonation, Deflagration, Equipment, Explosion, DDT

The code used for repair and alterations of an existing system depends on the code used for construction as well as on the requirements imposed by the jurisdiction. Note that getting a permit from the jurisdiction may be necessary for an extensive alteration.

Code of ConstructionGenerally Accepted Code for Repair and Alterations…
Category: Piping
Keywords: Piping, Codes

The requirements of the code used for the original construction apply. The piping may meet the requirements of more than one code. In which case, the code used for changing the rating may be different than the original code of construction. In any case, the re-rated system should meet all of the requirements of the selected code. Note that if the original proof test of the system was…

Category: Piping
Keywords: Codes, Piping, Requirements

At least three of the ASME B31 piping codes are logical choices:

  • ASME B31.1, Power Piping
  • ASME B31.3, Process Piping
  • ASME B31.12 Hydrogen Piping and Pipelines

Considerations for code selection include:

  • Requirements imposed by the authority having jurisdiction, whether by direct reference or…
Category: Piping
Keywords: Piping, Codes, Requirements

Several organizations published a paper together on this topic in 2017 (see attached). Based on comparisons with tests and CFD simulations, the following conclusions were drawn:

  1. The gas concentration for vapor cloud explosion blast load calculations for H2 jets can be limited to approximately 10% to 75%. Note that testing for H2-air VCEs in congested environments has been performed…
Category: Explosions
Keywords: Explosion, Ignition, Guidelines, Vapor Cloud

Hydrogen affects the mechanical properties of most materials. For example, hydrogen reduces the
fracture toughness and increases the fatigue crack growth rate in steels. There is a significant amount of
research, analytical work, and codes and standards development being undertaken to improve our
understanding of how these materials can be utilized in pipelines. The results of the…

Category: Piping
Keywords: Pipeline, Material Compatibility, ASME Standards, Pipeline Safety

Because cast irons are relatively brittle materials, they should generally be avoided in industrial and
transmission pipeline applications. In low pressure applications like residential distribution piping
systems, the use of cast irons is probably acceptable.

Category: Piping
Keywords: Cast Iron, Pipeline, Low-pressure systems, ASME Standards
We are professional and reliable provider since we offer customers the most powerful and beautiful themes. Besides, we always catch the latest technology and adapt to follow world’s new trends to deliver the best themes to the market.

Contact info

We are the leaders in the building industries and factories. We're word wide. We never give up on the challenges.

Recent Posts