What is your recommendation schedule for vent line opening inspection?
We would not open the vent system to inspect the internal piping without a good reason.
It is recommended to check for water in the vent stack trap
- At startup and daily during startup.
- On LH2 tank system, every delivery
- After the 1st rainstorm after a system is installed
- LH2 vent stacks after establishing the baseline above
- After every large venting event
- Quarterly unless baseline requires more frequent
- GH2 stack after baseline
- Check caps are still on quarterly for stationary tubes.