What are the typical criteria for determining the venting flow rates of LH2 facilities? For example, how quickly should LH2 be emptied in case of a potential BLEVE (boiling liquid expanding vapor explosion) caused by a fire near the LH2 storage tank?

There are several levels of documents which can be used to assist with the design, sizing, selection, and installation of the pressure relief device settings for LH2 tanks. 

Pressure vessel design codes, such as the ASME Boiler and Pressure Vessel Code will provide minimum requirements for design of pressure vessels (including LH2 tanks), relief devices, and relief systems. However, these codes will not provide the sizing criteria nor anticipate all of the potential demand cases that might be imparted upon a vessel. 

In the US, the model fire codes require compliance with NFPA 2, which then references documents such as CGA S1.2 and CGA S1.3 for sizing criteria. These documents have been customized by the industrial gas business specifically for cryogenic fluids such as LH2. API Standard 520 “Sizing, Selection and Installation of Pressure-Relieving Devices in Refineries” of is also a helpful document to provide additional guidance. 

For LH2 storage tanks, usually the highest process demand is an engulfing fire with a loss of vacuum insulation to atmosphere. This failure mode can result in additional heat flux from air condensation in the annular space which must also be addressed. 

It is not required to proactively vent the contents of an LH2 tank when exposed to fire. Relief devices are required to prevent the accumulation of internal pressure to unsafe levels. Within the ASME BPV, this is 121% of Maximum Allowable Working Pressure for scenarios involving fire exposure. It is common practice, but not required, that at least one device be non-reclosing (e.g. a rupture disc) for both managing the high flow required as well as to relieve the contents of the tank. Reclosing relief devices will maintain pressure in a fire and are more likely to lead to a vessel rupture if the fire ultimately weakens the pressure vessel.

LH2 tanks are unlikely to BLEVE due to the vacuum insulation outer jacket (usually carbon or stainless steel) preventing direct impingement of fire onto the main pressure vessel, as well as the internal cryogenic contents maintaining the main pressure vessel walls at a cooler temperature until the contents have been relieved by the relief devices. 

Category
Pressure Relief Devices
Keywords
Boiling Liquid Expanding Vapor Explosion (BLEVE)
LH2
Fire
NFPA 2
Storage
Pressure Relief Device