Skip to main content

What precautions should be taken for GH2 vent design concerning temperature?

The vent system should be designed for the temperature at which it operates (ambient for GH2 and Cryogenic for LH2). The outlet of the vent system should be designed for a fire to ensure the mechanical integrity of the vent system. 

The supports should also be designed for these temperatures and the associated expansion and contraction. 

It should be ensured that moisture cannot enter the vent system and freeze plugging the vent system, which may be a single point of failure.

Category
System Design
Keywords
GH2
Temperature
Vent System
Submission Year
2024
Month
01
We are professional and reliable provider since we offer customers the most powerful and beautiful themes. Besides, we always catch the latest technology and adapt to follow world’s new trends to deliver the best themes to the market.

Contact info

We are the leaders in the building industries and factories. We're word wide. We never give up on the challenges.

Recent Posts