Liquid hydrogen will almost never accumulate in a vent system since vent systems are typically designed without insulation. The extremely cold liquid hydrogen temperature of -420 F.
Additionally, vent stacks on an LH2 tank are connected to the vapor phase of the tank. Only in a few rare instances will LH2 be entrained in the gas stream.
Accumulators are recommended at the bottom of…
The deflagration pressure is dependent upon many variables.
However, some general concepts are:
Exhaust systems (sometimes referred to as ventilation systems) are used to exhaust hydrogen and air mixtures. Normally these are used to vent streams with less than flammable range hydrogen in air.
That is, hydrogen detectors trigger venting or the ventilation systems runs during all hydrogen operations. In these instances, low concentrations of hydrogen are expected, but deflagration is…
Relief device sizing for liquid hydrogen tanks follow recognized standards such as CGA S1.3. The sizing criteria include a worst-case scenario of an engulfing fire with loss of vacuum integrity.
LH2 tanks are unlikely to BLEVE due to the vacuum insulation outer jacket (usually carbon or stainless steel) preventing direct impingement of fire onto the main pressure vessel, as well as the…
Yes, there are differences due to the differences in the fluid properties. We’re not sure what is meant by blowdown. If this means that should the gases be vented to a vent stack, possibly, but for certain these need to be vented to a safe location.
There is currently a published ASME BPV Code Case describing pressure design requirements for pressure design of electrolyzers. If the Code Case is adopted by the jurisdiction where a new electrolyzer will be installed, the new electrolyzer will have to meet the requirements in the Code Case. The responsible ASME committee is working to revise the Code Case and intends to incorporate the Code…
Applicable EU Directives frequently include the following:
· Low Voltage - 2014/35/EU
· Machinery - 2006/42/EC
· Electromagnetic Compatibility - 2014/30/EU, EMC
· Pressure Equipment - 2014/67/EU
· Restriction of Hazardous…
When it is necessary or desirable to work on a part of a hydrogen system while another part of the system remains in operation or in standby condition. An example is a system with two compressors, where one is normally operating and the other acts as an installed spare. The two block valves are closed, and the bleed (vent) valve is open. This arrangement assures that any hydrogen leaking…
Recommended limits of heat flux for various exposures is provided in documents such as API Standard 521, the International Fire Code, the National Fire Protection Association and the Society of Fire Protection Engineers. Selection of a specific thermal radiation level is dependent upon a risk analysis. Some salient exposures are listed below.