The regulations for electrical classification in Europe and a US jurisdiction such as California are significantly different and should not be assumed to be the same. Consultation with Authorities Having Jurisdiction or a Third- Party expert regarding the application of the US National Electric Code is advised. Some additional important points:
The HSP has concerns with the use of…
There are no specific code resources that specifically cover hydrogen liquefaction plants, but they must be built to the general building, electrical, machinery, piping, and mechanical codes for process plants. Codes such as NFPA 2, Hydrogen Technologies Code, for installation and emergency response may also be used for reference. It may also be beneficial to break down the requirements into…
Panel members have not encountered a device or area classification for ATEX approval within Canada. ATEX is a European Union directive and is not generally recognized within North American standards. The second link below references a UL similarity. https://news.nilfiskcfm.com/2017/03/atex-certification-applicable-north-america/; https://www.ul.com/services/atex-certification-…
This production rate of hydrogen of about 96 kg/h is quite significant, which depending upon the application might require a significant amount of storage. There will be a need to determine how many kg the project wants to store from this production rate in order to determine how much hydrogen ground storage is needed. Since the project is in Europe, look for pressure vessel manufacturers that…
When it is necessary or desirable to work on a part of a hydrogen system while another part of the system remains in operation or in standby condition. An example is a system with two compressors, where one is normally operating and the other acts as an installed spare. The two block valves are closed, and the bleed (vent) valve is open. This arrangement assures that any hydrogen leaking…
Applicable EU Directives frequently include the following:
· Low Voltage - 2014/35/EU
· Machinery - 2006/42/EC
· Electromagnetic Compatibility - 2014/30/EU, EMC
· Pressure Equipment - 2014/67/EU
· Restriction of Hazardous…
There is currently a published ASME BPV Code Case describing pressure design requirements for pressure design of electrolyzers. If the Code Case is adopted by the jurisdiction where a new electrolyzer will be installed, the new electrolyzer will have to meet the requirements in the Code Case. The responsible ASME committee is working to revise the Code Case and intends to incorporate the Code…
Hydrogen cylinders contain pure hydrogen unless they are specifically manufactured for and marked as a mixture. The purity grade is usually between 99.5% and 99.9999%. The balance is typically inert gases (such as nitrogen) with just ppm levels of other contaminants, but this can vary depending upon the production source. When emptied, the residual is still the same purity of hydrogen, just at…
It is possible to store large quantities of gaseous hydrogen above ground, but it will likely require a large footprint due to its relatively low density even at high pressure. Also, if the quantity equals or exceeds 10,000 lb., the facility will need to comply with OSHA 1910.119 process safety management requirements if located in the US. Similar regulations exist in Europe and Asia that…