Facility management confirmed that a hydrogen gas cylinder did not comply with the limiting condition for operation (LCO) for flammable gas control systems in the lab's safety requirements. Earlier erroneous calculations had shown that a release of the entire contents of the cylinder into the hood could not reach the lower flammability limit (LFL).

The facility manager determined that the LCO was applicable and immediately entered the action statement in the safety system, which required immediate termination of normal operations in the affected wing of the building. Because normal operations had already been terminated in the wing for HVAC maintenance, further efforts to terminate normal operations were not necessary. The hydrogen cylinder was removed from the hood, thus view more

A health physics technician (HPT) discovered that a scaler in an analytical laboratory was out of P-10 gas (90%Ar and 10% CH4). The HPT went to the building where auxiliary gas cylinders are stored. He located a P-10 gas cylinder and turned to search for a hand-cart. There were no hand-carts present, and the technician had to get one from another room. When he returned to the cylinder storage area, he loaded the wrong cylinder. It contained hydrogen gas instead, however, the two cylinders were next to each other and they were basically identical. The empty cylinder was then replaced by the full one and the scaler was purged for several minutes before it was used. The alpha channel worked well, however, the beta channel did not respond. An instrument technician was contacted to identify view more

A hydrogen cylinder was initially located in an adjacent laboratory, with tubing going through the wall into the laboratory in use. When the cylinder was moved to the laboratory in use, a required leak check was not performed. Unfortunately, a leak had developed that was sufficient to cause an accumulation of hydrogen to a level above the Lower Flammability Limit. The hydrogen ignited when a computer power plug was pulled from an outlet. The exact configuration of the leak location and the outlet plug is unknown.