A deficiency was discovered in the application of a hydrogen sensor in the Rotary Mode Core Sampling (RMCS) portable exhauster. The sensor is installed in the flow stream of the exhauster designed to be used with a RMCS truck for core sampling of watch list tanks, and is part of the flammable gas detector system. During the previous week, a quarterly calibration of the sensor, per maintenance procedure, was attempted by Characterization Project Operations (CPO) technicians. Ambient temperatures during the sensor calibration were approximately 20 to 30 degrees F. Inconsistencies in calibration results and the failure of the sensor to meet the response-time calibration requirement lead to the conclusion that the unit could not reliably perform its safety function at low ambient view more