A process area alarm activated. The alarm was caused by an instrument channel located above a reaction vessel off-gas system final HEPA filter canister, which indicated 25% of the lower explosive limit (LEL) for hydrogen. Since the only source of hydrogen is from the reaction vessel during the reaction of sodium with concentrated sodium hydroxide, the immediate actions were to shutdown the reaction process and place the facility in a safe condition.

The root cause was inadequate or defective design. Had the pre-filter drains been vented to outside the building, no hydrogen could accumulate in the process area. The corrective action for this is to complete an Engineering Task Authorization (ETA) to install a sample/drain collection system with loop seals to prevent any release of view more

While attempting to light the hydrogen flare inside a Metalorganic Chemical Vapor Deposition (MOCVD) system burn box, a small explosion occurred, blowing the back section of the burn box off. Hydrogen flow was shut down immediately, and this MOCVD operation was suspended. Researchers made the determination that this was a minor incident and there were no injuries.

The follow-up investigation determined that the MOCVD HEPA filter had become sufficiently loaded to the point where performance of the burn box exhaust ventilation system was significantly degraded. The static pressure created across the "loaded" HEPA filter equaled the operating static pressure of the exhaust ventilation system servicing the burn box. This resulted in a region of "dead air" in the view more