A closed 20-mL glass scintillation vial containing approximately 5 grams of an aluminum hydride compound ruptured and shattered, likely due to pressure buildup after 6 weeks of storage. The glass vial with aluminum hydride compound was stored inside a closed plastic box. The plastic box with vial was stored within an air-free glove box at room temperature. When the glass vial ruptured, the vial was contained within the plastic box; however, the plastic box door was forced slightly ajar. The ruptured containers and internal materials were fully contained within the glove box. No damage was observed to the glove box and no one was injured. The attached photograph shows the remains of the vial within the plastic box.

A small research sample of approximately 5 grams of aluminum hydride (alane) doped with 2-3 mol % TiCl3 contained within a glass ampoule ruptured after transit while stored in an office cabinet. The rupture was attributed to over-pressurization caused by hydrogen gas buildup within the sample over a four-month period. The glass ampoule, contained within a 0.2-inch thick cardboard shipping tube, was not a pressure-rated container. The rupture resulted in glass chards penetrating the protective cardboard shipping tube. The aluminum hydride, a fine powder, was released from the shipping tube during the pressure release. The fine aluminum powder leaked from the cabinet and set off a local smoke alarm that brought emergency responders to the scene. No personnel were present in the area when view more