Skip to main content

Category

Detectors, Storage, System Design

Category

Detectors, Storage, System Design

The containerized electrolysis unit should be installed per manufacturer instructions, the requirements
of its listing such as to ISO 22734, Hydrogen generators using water electrolysis - Industrial, commercial,
and residential applications, and NFPA 2, Hydrogen Technologies Code. A primary consideration for
indoor installation is the potential for hydrogen releases from the system,…

Category: System Design

Composite cylinders can be manufactured to standards written by CSA, ASME, and ISO depending on the application and local requirements. Several ISO standards can serve as the basis for composite cylinder approvals within North America.

Category: Storage

The suspected cause was a mixture of oxygen and hydrogen that passed downstream from the electrolysis unit into several storage vessels. Hydrogen-oxygen mixtures are very hazardous. Subsequent ignition resulted in internal pressure that exceeded the limits of the storage system. The design of electrolyzers, detection of upset conditions, and preventing the accumulation of oxygen within the…

Category: System Design

Speed of detection, detection limit, location, and cross-sensitivity are some of many criteria that might be used for selecting a detector. A common setpoint for gaseous hydrogen detection is 25% of LFL, or 1% concentration in air. However, the detection limit also depends on the system and exposure. When specific hazards are likely, detectors may have detection limits in the low-ppm range.…

Category: Detectors

Leakage/loss depends on the vessel design. Metallic or metallic lined vessels have extremely low permeability and losses through the vessel walls are typically imperceptible. Conversely, Type IV composite vessels which have non-metallic liners are subject to permeation. They are required to meet maximum permeation rates as part of their certification. Fugitive emissions from piping systems can…

Category: Storage

Leak detection system requirements depend on the system design and applicable codes. The
appropriateness of detection equipment depend on many factors, including the type of system,
application, location, and probability of leaks. For example, hydrogen refueling stations are required by
code to be equipped with leak detection systems.

Category: Detectors

While hydrogen gas detectors are less effective outdoors, they can be an important safeguard as part of an overall hydrogen system design. They have been used in many cases to automatically shut down equipment and isolate hydrogen supply. Location and type of detectors depend on the system design and siting, but when installed, should be in areas that are most likely to be exposed to hydrogen…

Category: Detectors

Training personnel and equipping them with portable gas detectors to properly identify the gas that is
leaking can play an important role in both troubleshooting and emergency response.

Category: Detectors

The manufacturer’s calibration requirements should be followed to ensure proper operation of the
detection system. The requirements will vary depending on the type of detector and the environment in
which they are installed. Calibration can usually be performed by the user/owner if properly trained and
supplied with calibration gas, etc.

Category: Detectors
We are professional and reliable provider since we offer customers the most powerful and beautiful themes. Besides, we always catch the latest technology and adapt to follow world’s new trends to deliver the best themes to the market.

Contact info

We are the leaders in the building industries and factories. We're word wide. We never give up on the challenges.

Recent Posts